13. Protection
Control
13.1 Protection Control for All Operations
13.1.1 Time Delay Safety Control
1 The compressor will not start for three minutes after stop of operation.
13.1.2 30 Seconds Forced Operation
1 Once the compressor starts operation, it will not stop its operation for 30 seconds.
2 However, it can be stopped using remote control.
13.1.3 Total Running Current Control
1 When the mono bloc unit running current exceeds X value, the compressor frequency will decrease.
2 If the mono bloc unit running current does not exceed X value, the compressor frequency will return to
normal operating frequency.
3 If the mono bloc unit running current continue to increase till exceed Y value, compressor will stop, and if this
occurs 3 times within 20 minutes, system will stop operation and OFF/ON remote control LED will blink (F16
error occurs).
09C 12C 14C 16C
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Heating
6.2 10.6 7.4 10.6 8.0 10.6 8.5 10.6
13.1.4 IPM (Power Transistor) Prevention Control
A. Overheating Prevention Control
1 When the IPM temperature rises to 95°C, compressor will stop immediately.
2 Compressor will restart delay 3 minutes when the IPM temperature decreases to 90°C.
If this condition repeats continuously 3 times within 30 minutes, system will stop operation and OFF/ON
remote control LED will blink (F22 error occurs).
B. DC Peak Current Control
1 When the current to IPM exceeds set value of 40.1 ± 5.0 A (MDF09C), 44.7 ± 5.0 A (MDF12C, MDF14C,
MDF16C), compressor will stop. Compressor will restart after three minutes.
2 If the set value exceeds again for more than 30 seconds after the compressor restarts, operation will restart
after two minutes.
3 If the set value exceeds again for within 30 seconds after the compressor restarts, operation will restart after
one minute. If this condition repeats continuously for seven times, system will stop operation and OFF/ON
remote control LED will blink (F23 error occurs).
13.1.5 Compressor Overheating Prevention Control
The compressor operating frequency is regulated in accordance to compressor tank temperature as shown in
below figures. When the compressor tank temperature exceeds 112°C, compressor will stop, and if this occurs
4 times within 30 minutes, system will stop operation and OFF/ON remote control LED will blink (F20 error
occurs).
Summary of Contents for WH-MDF09C3E8
Page 14: ...14 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 15: ...15 4 1 1 Main Components ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 3 Weekly Timer Setting ...
Page 20: ...20 4 1 4 Setting Up The Special Functions ...
Page 21: ...21 5 Dimensions 5 1 Mono Bloc Unit ...
Page 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 25: ...25 7 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 27: ...27 ...
Page 28: ...28 8 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 29: ...29 ...
Page 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 31: ...31 ...
Page 32: ...32 9 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 33: ...33 ...
Page 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Page 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 37: ...37 10 2 1 1 Noise Filter Printed Circuit Board ...
Page 38: ...38 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 39: ...39 Main Components ...
Page 49: ...49 ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 66: ...66 ...
Page 123: ...123 ...