2 Booster heater Turn Off condition:
o
Tank temperature > Tank set tempe
[0
°
C]
for continuous 15 secs
o
When BOOSTER HEATER DELAY TIMER start count after switch from heating heat-up interval to tank
heat-up interval
* DELAY TIMER can be set by remote control.
12.11 Base Pan Heater Control (Optional)
To enable the base pan heater function, pin 3 of SW2 of water system PCB has to be switched from OFF to ON
position.
Base pan heater ON condition:
o
When outdoor ambient temperature
≤
3°C AND
o
Deice operation ON
Base pan heater will continue ON for 10 minutes after deice operation ends.
Base pan heater OFF condition:
o
When outdoor ambient temperature > 3°C OR
o
When operation is not heating OR
o
Base pan heater ON timer count completed
12.12 Three Way Valve Control
Purpose:
- 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side
Control
contents:
1 3 ways valve switch Off:
o
During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
2 3 ways valve switch On:
o
During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
3 Stop
condition:
o
During stop mode, 3 ways valve will be in switch off position
Base pan heater (85W)
Summary of Contents for WH-MDF09C3E8
Page 14: ...14 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 15: ...15 4 1 1 Main Components ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 3 Weekly Timer Setting ...
Page 20: ...20 4 1 4 Setting Up The Special Functions ...
Page 21: ...21 5 Dimensions 5 1 Mono Bloc Unit ...
Page 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 25: ...25 7 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 27: ...27 ...
Page 28: ...28 8 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 29: ...29 ...
Page 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 31: ...31 ...
Page 32: ...32 9 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 33: ...33 ...
Page 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Page 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 37: ...37 10 2 1 1 Noise Filter Printed Circuit Board ...
Page 38: ...38 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 39: ...39 Main Components ...
Page 49: ...49 ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 66: ...66 ...
Page 123: ...123 ...