Setting 2: When heating priority is not set by remote control:
When Solar Priority is set / not set by remote control:
1 3 ways valve control:
o
3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank
heat-up interval. Both mode will switch alternatively. Tank mode is the Initial running mode of this heat +
tank mode (heating no priority).
2 Heat pump operation control:
o
During heating heat-up interval
- Follow normal heating operation.
Under solar priority set condition:
- Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo
OFF
AND
solar 3WV OFF
AND
Tank temperature < THERMO ON TEMP (End Room Interval
Early)
OR
- Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature <
THERMO ON TEMP
AND
solar 3WV OFF
Under solar priority not set condition:
- Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo
OFF
AND
Tank temperature < THERMO ON TEMP (End Room Interval Early)
OR
- Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature <
THERMO ON TEMP
* THERMO ON TEMP is defined form following Case1 to Case4.
o
During tank heat-up interval
- Heat pump tank target temperature = Tank set temperature or [50°C] whichever lower
- Heat pump Water Outlet set temperature is set to Maximum [55°C] during tank interval
- Initial Tank THERMO ON TEMP = heat pump tank target tempe
[-1°C]
Case 1:
- THERMO OFF TEMP:
1.
THERMO OFF TEMP = Heat pump tank target tempe
[+1
°
C]
.
2.
Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump off due to water
thermo, switch 3 ways valve to room side. End Tank heat-up interval and start count heating heat-up
interval.
- THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-1
°
C]
.
2.
After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval
when tank temperature < THERMO ON TEMP
Case 2:
- Heat pump THERMO OFF TEMP:
1.
Heat pump THERMO OFF TEMP = 53°C +
[+4
°
C]
.
2.
Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump
OFF.
- THERMO ON TEMP:
1.
THERMO ON TEMP = Water inlet temperature, when heat pump thermo off +
[-3
°
C]
.
Case 3:
- Heat pump THERMO OFF TEMP:
1.
Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
- THERMO ON TEMP:
1.
THERMO ON TEMP = Water inlet temperature < 55°C.
Case 4 (Only during solar priority is set condition):
When solar pump ON, tank heat-up interval end early and 3 ways valve switch to room side.
- THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-1
°
C]
.
2.
After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval
when tank temperature < THERMO ON TEMP and solar 3 way valve OFF.
Summary of Contents for WH-MDF09C3E8
Page 14: ...14 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 15: ...15 4 1 1 Main Components ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 3 Weekly Timer Setting ...
Page 20: ...20 4 1 4 Setting Up The Special Functions ...
Page 21: ...21 5 Dimensions 5 1 Mono Bloc Unit ...
Page 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 25: ...25 7 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 27: ...27 ...
Page 28: ...28 8 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 29: ...29 ...
Page 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Page 31: ...31 ...
Page 32: ...32 9 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Page 33: ...33 ...
Page 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Page 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 37: ...37 10 2 1 1 Noise Filter Printed Circuit Board ...
Page 38: ...38 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 39: ...39 Main Components ...
Page 49: ...49 ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 66: ...66 ...
Page 123: ...123 ...