Floor h Swimming pool
Connect floor heating and swimming pool to 2 circuits through buffer tank as shown in figure.
Install mixing valves, pumps and thermistors (specified by Panasonic) on both circuits.
Then, install additional pool heat exchanger, pool pump and pool sensor on pool circuit.
Install the remote controller in room where floor heating is installed. Circulation water temperature of floor heating
and swimming pool can be set independently.
Install buffer tank sensor on buffer tank.
It requires connection setting of buffer tank and
∆
T temperature setting at heating operation separately. This system
requires the optional PCB (CZ-NS4P).
Must connect swimming pool to “Zone 2”.
If it is connected to swimming pool, operation of pool will stop when “Cooling” is operated.
Swimming pool only
This is an application that connects to the swimming pool only.
Connects pool heat exchanger directly to Mono bloc without using buffer tank.
Install pool pump and pool sensor (specified by Panasonic) at secondary side of the pool heat exchanger.
Install the remote controller in room where floor heating is installed.
Temperature of swimming pool can be set independently.
This system requires the optional PCB (CZ-NS4P).
In this application, cooling mode cannot be selected. (not display on remote controller)
Thermistor 1
Heat EXT
Thermistor
3
Thermistor 2
Buffer tank
Pump 2
Pump
3
Pump 1
Mixing
valve 1
Mixing
valve 2
Mono bloc
Floor heating 1
Swimming pool
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Room thermostat
Internal
Zone 2
Swimming pool
T
Thermistor
Pump
Swimming pool
Heat EXT
Mono bloc
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 1 Zone system
Zone :Swimming pool
T