84
Auto
Tank
12.4.5 Service
Setup
30. Outdoor temp. for (Heat to Cool)
Initial setting: 15°C
15°
C
Heat
Cool
Outdoor temp. rising
Set outdoor temp that switches from heating to cooling by Auto setting.
Setting range is 5°C
~
25°C
Timing of judgement is every 1 hour
31. Outdoor temp. for (Cool to Heat)
Initial setting: 10°C
10°
C
Heat
Cool
Outdoor temp. dropping
Set outdoor temp that switches from Cooling to Heating by Auto setting.
Setting range is 5°C
~
25°C
Timing of judgement is every 1 hour
32. Floor operation time (max.)
Initial setting:
8
h
Heat
Tank
3
0min
~
10h
Set max operating hours of heating.
When max operation time is shortened, it can boil the tank more fre
q
uently.
It is a function for H Tank operation.
33. Tank heat up time (max.)
Initial setting: 60min
Heat
Tank
5min
~
4h
Set max boiling hours of tank.
When max boiling hours are shortened, it immediately returns to Heating operation, but it may
not fully boil the tank.
34. Tank re-heat temp.
Initial setting: -
8
°C
-12°C
~
-2°C
Set temp to perform reboil of tank water.
Setting range is -12°C
~
-2°C
35. Sterilization
Initial setting: 65°C 10min
Set timer to perform sterilization.
1
Set operating day & time. (Weekly timer format)
2
Sterilization temp (55
~
75°C If use back-up heater, it is 65°C)
3
Operation time (Time to run sterilization when it reached setting temp 5min
~
60min)
User shall set whether to use or not to use sterilization mode.
36. Pump maximum
s
peed
Initial setting: Depend on model
Service setup
12:00am,Mon
Flow rate
Max. Duty
Operation
88
:
8
L/min
0xCE
Air Purge
Select
Normally setting is not necessary.
Please adjust when need to reduce the pump sound etc.
Besides that, it has Air Purge function.
When
*
Pump fl ow setting is Max. Duty, this duty set is the fi x pump duty run during room side
operation.
37. Pump down
Service setup
17:26, Wed
Pump down:
ON
Confi rm
Service setup
12:00am,Mon
Pump down:
ON
Confi rm
Pump down operation
in progress!
OFF
Operate pump down operation
38. Dry concrete
30°C
1
2
3
4
5
6
35°C
35°C
40°C
40°C
45°C
Stage
Operate concrete curing operation.
Select Edit, set temp for every stage (1
~
99 1 is for 1 day).
Setting range is 25
~
55°C
When it is turned ON, dry concrete starts.
When it is 2 zone, it dries both zones.
39. Service contact
Contact-1: Bryan Adams
ABC/ abc
0-9/ Other
A B C D E F G H I J K L M N O P Q R
S T U V W X Y Z
a b c d e f g h i
j k l m n o p
q
r s t u v w x y z
Select
Enter
Service setup
12:00am,Mon
Service contact:
Contact 1
Contact 2
Select
Confi rm
Able to set name & tel no. of contact
person when there is breakdown etc. or
client has trouble. (2 items)