132
Control detail:
During operation ON at Heat Mode
o
Boiler signal turns ON when
Outdoor ambient < Outdoor Ambient Set
AND
Buffer tank temperature < Target Buffer Tank Tempe [START_TEMP] for [START_TIMER]
AND
Heat pump operate at room side
AND
Connection of Boiler to Heating Select "YES" From installer menu
AND
Buffer Tank connection select "YES"
AND
Boiler prohibit flag = 0
o
Boiler signal turns OFF when
Outdoor ambient > Outdoor Ambient Set + [-2°C]
OR
Buffer Tank temperature > Target Buffer Tank tempe [STOP_TEMP] for [STOP_TIMER]
OR
Heat pump not at room side.
OR]
Boiler prohibit flag = 1
During operation ON at Tank Mode
o
Boiler signal turns ON when
Outdoor ambient < Outdoor Ambient Set
AND
Heat pump operate at tank side for continuous | DELAY_TIMER |
AND
Connection of Boiler to DWH Tank select "YES" from installer menu.
AND
Boiler prohibit flag = 0
o
Boiler signal turns OFF when
Outdoor ambient > Outdoor Ambient Set + [2°C]
OR
Heat pump not operates at tank side.
OR
Boiler prohibit flag = 1
SG ready Control Mode:
o
Using same SG ready from Sub Board input to control boiler ON/OFF output.
* When this SG ready is select for bivalent control, default SG ready function will change to control bivalent
output.
o
Remote controller can set the External Pump ON/OFF like bivalent alternative mode.
Control Content
Indoor will follow the SG ready bit input to control ON/OFF heat pump and boiler
00
: Heat pump OFF, Boiler OFF
10 : Heat pump OFF, Boiler ON
01
: Heat pump ON, Boiler OFF
11 : Heat pump ON, Boiler ON
* External pump will turn ON when the external pump selection is ON when boiler is ON even heat pump is OFF.
Boiler prohibit flag control
Purpose:
o
For product safety. Boiler signal is OFF when water temperature is too high.
Start condition:
o
Water
outlet
≥
85°C continues for 5 minutes.
o
Water
inlet
≥
85°C continues for 5 minutes.
o
Zone1
water
temp
≥
75°C continues for 5 minutes.
o
Zone2
Water
temp
≥
75°C continues for 5 minutes.
Contents:
After start condition fulfilled, set boiler prohibit flag = 1
Cancel condition:
o
After 30 minutes from start condition fulfilled.
Contents: