15
Item
Unit
Water System
Performance Test Condition
EN 14511 / EN14825
Operation Range
Outdoor Ambient
°C
Cooling: 10 ~ 43
Heating: -20 ~ 35
Water Outlet
°C
Cooling: 5 ~ 20
Heating: 20 ~ 55 ( Below Ambient -15°C)
20 ~ 60 (Above Ambient -10°C)
Internal Pressure Differential
kPa
Cooling: 22.0
Heating: 22.0
Water Pipe Connector (in.)
(1-1/4)
Water Drain Hose Inner Diameter
mm (inch)
15.0 (19/32)
Pump
Motor Type
DC Motor
Input Power
W
173
Hot Water Coil
Type
Brazed Plate
No. of Plates
36
Size (H × W × L)
mm
68.3 × 121 × 333
Water Flow Rate
l/min (m
3
/h)
Cooling: 20.1 (1.2)
Heating: 20.1 (1.2)
Pressure Relief Valve Water Circuit
kPa
Open: 300, Close: 210 and below
Flow Switch
Electronic Sensor
Protection Device
A
Residual Current Circuit Breaker (40)
Expansion Vessel
Volume
I
6
MWP
bar
3
Capacity of Integrated Electric Heater
kW
3.00
Note:
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled indoor water inlet
temperature of 12°C and water outlet temperature of 7°C.
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb
(42.8°F Wet Bulb) with controlled indoor water inlet temperature of 30°C and water outlet temperature of 35°C.
Specification are subjected to change without prior notice for further improvement.
Flow rate indicated are based on nominal capacity adjustment of leaving water temperature (LWT) 35°C and
=5°C
*** The sound power level is measured with accordance to EN12102 under conditions of the EN14825.