58
Terminal screw on PCB
Maximum tightening torque cN•m {kgf•cm}
M3 50
{5.1}
M4 120
{12.24}
12.1.5 Installation of Remote Controller
Installation
Location
12.1.5.1
Install at the height of 1 to 1.5 m from the floor (Location where average room temperature can be detected).
Install vertically against the wall.
Avoid the following locations for installation.
1 By the window, etc. exposed to direct sunlight or direct air.
2 In the shadow or backside of objects deviated from the room airflow.
3 Location where condensation occurs (The Remote Controller is not moisture proof or drip proof.)
4 Location near heat source.
5 Uneven
surface.
Keep distance of 1 m or more from the TV, radio and PC. (Cause of fuzzy image or noise)
Remote
Controller
Wiring
12.1.5.2
Remote Controller cable shall be (2 x min 0.3 mm
2
), of double insulation PVC-sheathed or rubber sheathed cable.
Total cable length shall be 50 m or less.
Be careful not to connect cables to other terminals (e.g. power source wiring terminal). Malfunction may occur.
Do not bundle together with the power source wiring or store in the same metal tube. Operation error may occur.
How to guide optional cables to control board
Guide cables through