83
z
Rated
specifications
Three-phase 400V type
Product No.
Applied
motor output
Rated output
current
Rated output
capacity
Power supply
capacity
Mass
BFV00074
0.75 kW
2.1 A
1.7 kVA
2.6 kVA
1.4 kg
BFV00154
1.5 kW
3.8 A
3.0 kVA
3.6 kVA
1.4 kg
BFV00224
2.2 kW
5.4 A
4.3 kVA
6.4 kVA
1.4 kg
BFV00374
3.7 kW
8.7 A
Note 1)
6.9 kVA
10.4 kVA
2.1 kg
Note 1)
The rated output current for the 3.7kW capacity is that for when the carrier
frequency is 7.5kHz or less.
When using at 10.0kHz, the rated output current must be reduced by 10%.
(When set to 10kHz: rated output current
×
0.9 = 7.83A)
Note 2)
The rated output capacity is that for the output voltage 460V.
Note 3)
The power supply capacity will change according to the impedance on the power
supply side. Prepare a power supply larger than the values given in the table.
z
Standard
specifications
Three-phase 400V type
Applied motor output
0.75 to 3.7kW
Rated output
voltage
3-phase, 380 to 460VAC (proportional to power supply voltage)
Ra
te
d
output
Overload current
rating
150% of rated output current for 1 minute
Number of phases,
voltage, frequency
3-phase, 380 to 460VAC: 50/60Hz
Tolerable voltage
variations
+10%, -15% of rated AC input voltage
Tolerable
frequency
variations
±5% of rated input frequency
Input pow
er supply
Instantaneous
voltage drop
resistance
capacity
·
Continuous operation at 323V or more
·
Continuous operation at less than 323V for 15 ms.
Specifications