Display
Details and cause of faults
Remedies
AU
• An auxiliary stop signal was
input from control circuit
terminal
• Check the sequence circuit to
confirm that the auxiliary stop
signal is correct.
OP
• The power was turned ON while
the run signal was ON
• The run signal was turned ON
while setting data in the
stopped mode, or the mode
was returned to the operation
mode with the MODE button
• Check the power loss start mode
(parameter P48)
• Check the run signal when the
data is being set
CPU
• Excessive noise was applied
on the inverter
• Reduce the noise around the
inverter
Note)
Refer to "Troubleshooting (1) and (2)" on pages 76 and 78.