Setting the frequency and forward/reverse run operation with the
operation panel
There are two methods for setting the frequency and carrying out forward/
reverse run operation with the operation panel.
·
Frequency setting:
"Potentiometer setting method",
"Digital setting method"
·
Forward/reverse run operation: "Forward run/reverse run method",
"Start/ stop, rotation direction mode
setting method"
1. Setting the frequency
1) Potentiometer setting method (Parameter P09 set to "0": Factory setting)
Set with the rotation angle of the frequency setting dial on the panel. The
operation will stop at the Min. position (0V stop: refer to page 73), and
the maximum frequency will be attained at the Max. position.
2) Digital setting method (Parameter P09 set to "1")
Press the MODE button on the panel to enter the frequency setting mode
(Fr). Press the SET button, set the frequency to be set with the (up)
button and (down) button, and then press the SET button to enter the
data.
The frequency can be changed by holding down the (up) button and
(down) button during operation. (Hereafter, this function is called the
MOP function.)
This MOP function cannot be used when parameter P08 is set to "1".