![Panasonic U-72MF1U9 Technical Data Manual Download Page 79](http://html.mh-extra.com/html/panasonic/u-72mf1u9/u-72mf1u9_technical-data-manual_268940079.webp)
3WAY VRF SYSTEM Unit Specifi cations
4
- 5
1
2
3
4
5
6
7
8
1. Outdoor Unit
Unit Specifi cations (4)
MODEL NAME
3WAY SYSTEM Capacity Control Outdoor Unit <14-Ton>
GENERAL MODEL No.
WU-168MF1U9, WU-168MF1U9E
COMPONENT OUTDOOR UNIT
U-72MF1U9, U-72MF1U9E*
U-96MF1U9, U-96MF1U9E*
SOURCE
208-230V/3N/60Hz
208-230V/3N/60Hz
PERFORMANCE
Cooling capacity
BTU / h (kW)
168,000 (49.2)
Heating capacity
BTU / h (kW)
189,000 (55.4)
UNIT DIMENSIONS
Height
in. (mm)
82-9/16 (2097)
Width
in. (mm)
74 (1880)
Depth
in. (mm)
Ceiling dimension : 35 ~ +2-3/8
(890 ~ +60)
Net weight
lbs. (kg)
573 (260)
672 (305)
Color (Munsell code)
Silky shade (1Y 8.5 / 0.5)
ELECTRICAL RATINGS
Voltage rating
V
208
230
Cooling
Running amperes
A
38.3
35.8
Power input
kW
13.1
13.1
Power factor
%
94.6
91.6
Heating
Running amperes
A
41.9
39.1
Power input
kW
14.4
14.4
Power factor
%
95.4
92.3
Starting amperes
A
157
152
COMPRESSOR
Type - Q'ty
Inverter driven Rotary type x 1
Inverter driven Rotary type x 1
+ Fixed Speed Scroll type x 1
Motor output
kW
4.1
2.7 + 3.75
Refrigeration oil
Type
FV68S (Ether oil)
Charge amount
gal
1.40 (5.3 liters)
1.96 (7.4 liters)
Crankcase heater
W
25
25 + 32
Capacity control
%
–
Refrigerant amount at shipment
lbs. (kg)
R410A - 25.9 (11.8)
R410A - 25.9 (11.8)
Refrigerant control
Electronic expansion valve
Defrost method
Reverse-cycle defrost, outdoor unit cycle defrost
Heat exchanger
Aluminum plate fin / Copper tube
FAN DEVICE
Type - Q'ty
Propeller fan x 1
Propeller fan x 1
Air circulation
CFM
5,300
5,650
External static pressure
in.WG
0
0
Motor output (No. of poles)
kW
0.7/8P
0.7/8P
Protective devices
High pressure switch, overcurrent (CT method)
TUBING
Refrigerant tubing
Suction tube
in. (mm)
ø1-1/8 (ø28.58) (Brazing)
Discharge tube
in. (mm)
ø7/8 (ø22.22) (Brazing)
Liquid tube
in. (mm)
ø5/8 (ø15.88) (Brazing)
Balance tube
in. (mm)
ø3/8 (ø9.52) (Flare nut)
Drain port
–
External air temperature operation range
°F
Cooling: 14 ~ 113 °F (DB)
Heating: -4 ~ 59 (WB)
Operation sound (Hi)
dB-A
58.0 (Quiet mode: 55.0)
Primary accessories
Connection tubing
ø7/8 (ø22.22) - ø3/4 (ø19.05)
Connection tubing
ø1-1/8 (ø28.58) - ø3/4 (ø19.05)
ø7/8 (ø22.22) - ø3/4 (ø19.05)
ø3/4 (ø19.05) - ø5/8 (ø15.88)
* Outdoor unit model name ended with the letter “E”
Refer to the Section 1 “3. Salt-Air Damage Resistant Specifications.”
Rated conditions
Performance, electrical characteristics values and operating sound are based on JIS B8616 package A/C.
(Cooling : Indoor intake air temperature 80°F DB / 67°F WB. Outdoor intake air temperature 95°F DB.)
(Heating : Indoor intake air temperature 70°F DB. Outdoor intake air temperature 47°F DB / 43°F WB.)