3WAY VRF SYSTEM Unit Specifi cations
4
- 3
1
2
3
4
5
6
7
8
1. Outdoor Unit
Unit Specifi cations (2)
MODEL NAME
3WAY SYSTEM Capacity Control Outdoor Unit <8-Ton>
MODEL No.
U-96MF1U9, U-96MF1U9E*
SOURCE
208-230V/3N/60Hz
PERFORMANCE
Cooling capacity
BTU / h (kW)
96,000 (28.1)
Heating capacity
BTU / h (kW)
108,000 (31.6)
UNIT DIMENSIONS
Height
in. (mm)
82-9/16 (2097)
Width
in. (mm)
35 (890)
Depth
in. (mm)
Ceiling dimension : 35
(890)
Net weight
lbs. (kg)
672 (305)
Color (Munsell code)
Silky shade (1Y 8.5 / 0.5)
ELECTRICAL RATINGS
Voltage rating
V
208
230
Cooling
Running amperes
A
23.2
21.6
Power input
kW
7.75
7.75
Power factor
%
92.8
90.2
Heating
Running amperes
A
25.4
23.7
Power input
kW
8.60
8.60
Power factor
%
94.0
91.2
Starting amperes
A
140
136
COMPRESSOR
Type - Q'ty
Inverter driven Rotary type x 1 + Fixed Speed Scroll type x 1
Motor output
kW
2.7 + 3.75
Refrigeration oil
Type
FV68S (Ether oil)
Charge amount
gal
1.96 (7.4 liters)
Crankcase heater
W
25 + 32
Capacity control
%
8 - 100 %
Refrigerant amount at shipment
lbs. (kg)
R410A - 25.9 (11.8)
Refrigerant control
Electronic expansion valve
Defrost method
Reverse-cycle defrost, outdoor unit cycle defrost
Heat exchanger
Aluminum plate fin / Copper tube
FAN DEVICE
Type - Q'ty
Propeller fan x 1
Air circulation
CFM
5,650
External static pressure
in.WG
0
Motor output (No. of poles)
kW
0.7/8P
Protective devices
High pressure switch, overcurrent (CT method)
TUBING
Refrigerant tubing
Suction tube
in. (mm)
ø7/8 (ø22.22)
*1
(Brazing)
Discharge tube
in. (mm)
ø3/4 (ø19.05) (Brazing)
Liquid tube
in. (mm)
ø3/8 (ø9.52) (Brazing)
Balance tube
in. (mm)
ø3/8 (ø9.52) (Flare nut)
Drain port
–
External air temperature operation range
°F
Cooling: 14 ~ 113 °F (DB)
Heating: -4 ~ 59 (WB)
Operation sound (Hi)
dB-A
55.0 (Quiet mode: 52.0)
Primary accessories
Connection tubing
ø1-1/8 (ø28.58) - ø3/4 (ø19.05)
ø7/8 (ø22.22) - ø3/4 (ø19.05)
ø3/4 (ø19.05) - ø5/8 (ø15.88)
* Outdoor unit model name ended with the letter “E”
Refer to the Section 1 “3. Salt-Air Damage Resistant Specifications.”
*1 If the size of tubing (LA) is less than 16.4 feet, it is recommended that the tubing diameter be larger than
ø
1-1/8" (
ø
28.58).
Rated conditions
Performance, electrical characteristics values and operating sound are based on JIS B8616 package A/C.
(Cooling : Indoor intake air temperature 80°F DB / 67°F WB. Outdoor intake air temperature 95°F DB.)
(Heating : Indoor intake air temperature 70°F DB. Outdoor intake air temperature 47°F DB / 43°F WB.)
TD831158-00̲3WAY̲VRF̲SYS.indb 3
TD831158-00̲3WAY̲VRF̲SYS.indb 3
2011/12/12 17:22:40
2011/12/12 17:22:40