Example of Connection
Appendix
249
4. Example of Connection
Example of connection
(Connection of 8 indoor units Heat pump system)
Branch with refnet joint
Branch with refnet joint and refnet header
Branch with refnet header
Maximum
allowable
length
Between outdoor and
indoor units
Actual pipe length
Pipe length between outdoor and indoor units 150 m
[Example] unit 8: a+b+c+d+e+f+g+p 150 m
[Example] unit 6: a+b+h 150 m, unit 8: a+i+k 150 m
[Example] unit 8: a+i 150 m
Equivalent length
Equivalent pipe length between outdoor and indoor units 175 m (Assume equivalent pipe length of refnet joint to be 0.5 m and of the refnet header to be 1.0 m. (for calculation purposes))
Total extension
length
Total piping length from outdoor unit to all indoor units between 10 m and 300 m
Allowable
height
Between outdoor and
indoor units
Difference in
height
Difference in height between outdoor and indoor units (H1) 50 m (40 m if outdoor unit is located in a lower position).
Between indoor and indoor
units
Difference in
height
Difference in height between adjacent indoor units (H2) 15 m
Allowable length after the branch
Actual pipe length
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit 40 m
[Example] unit 8: b+c+d+e+f+g+p 40 m
[Example] unit 6: b+h 40 m, unit 8: i+k 40 m
[Example] unit 8: i 40 m
Refrigerant branch kit selection
Refrigerant branch kits can only be used with R-410A.
Use the following refnet joint
Use the following refnet header
Pipe size selection
Caution on selecting connection pipes
If the overall equivalent piping length is 90 m, be sure to
enlarge the pipe diameter of the gas-side main piping. If the
recommended pipe size is not available, stick to the original
pipe diameter (which may result in a small capacity decrease).
[Gas side]
U-4..5ML5: Ø15.9.Ø19.1
U-6ML5: Ø19.1.Ø22.2
A. Piping between outdoor unit and refrigerant branch kit
• Match to the size of the connection piping on the outdoor unit.
Outdoor unit connection piping size
B. Piping between refrigerant branch kits
•
Use the pipe size from the following table.
C. Piping between refrigerant branch kit and indoor unit
• Pipe size for direct connection to indoor unit must be the same as the
connection size of indoor unit.
How to calculate the additional refrigerant to be charged
Additional refrigerant to be charged R (kg)
R should be rounded off in units of 0.1 kg
indoor unit
refnet joint
refnet header
a
b
c
d
e
f
g
h
i
j
k
l
m
n
1
2
3
4
5
6
7
8
H2
H1
p
A
B
C
D
E
F
G
H1
H2
a
i
b
c
d
e
f
g
h
1
2
3
4
5
6
k
j
7
8
A
B
a
H1
H2
c
d
e
f
g
h
i
b
1
2
3
4
5
6
7
8
Outdoor unit capacity type
Refrigerant branch kit name
U-4..6ML5 CZ-P20BK32Q
Outdoor unit capacity type
Refrigerant branch kit name
U-4..6ML5 CZ-P29HK32Q
Main pipe
(enlarge)
First refrigerant
branch kit
Indoor
unit
Outdoor unit
capacity type
Piping size (outer diameter x minimum
thickness)
Gas pipe
Liquid pipe
U-4..5ML5 Ø15.9x1.0
(Ø19.1x1.0)
Ø9.5x0.8
U-6ML5 Ø19.1x1.0
(
Ø22.2x1.0)
Piping size (outer diameter x minimum thickness)
Gas pipe
Liquid pipe
Ø15.9x1.0 Ø9.5x0.8
Indoor capacity
index
Piping size
(outer diameter x minimum thickness)
Gas pipe
Liquid pipe
20+25+32+40+50 Ø12.7x0.8 Ø6.4x0.8
63+80+100+125 Ø15.9x1.0 Ø9.5x0.8
R=
(
Total length (m) of liquid
p
iping size at Ø9.5
)
x0.054+
(
Total length (m) of liquid
piping size at Ø
6.4
)
x0.022
Example for refrigerant branch using refnet joint and refnet header
R=[73 x 0.054] + [69 x 0.022] = 5.46
5.5 kg
a: Ø9.5x30 m d: Ø9.5x13 m g: Ø6.4x10 m j: Ø6.4x10 m
b
: Ø9.5x10 m e: Ø6.4x10 m h: Ø6.4x20 m k: Ø6.4x9 m
c: Ø9.5x10 m f: Ø6.4x10 m i: Ø9.5x10 m
Panasonic
Summary of Contents for U-4..6ML5XPQ
Page 1: ...Service Manual U 4 6ML5XPQ DPQ Urban Multi Mini UM Heat Pump ...
Page 2: ......
Page 12: ...Introduction x Urban Multi ML5 Mini UM Heat Pump ...
Page 37: ...Specifications Specifications 25 Panasonic ...
Page 38: ...Specifications 26 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Page 39: ...Specifications Specifications 27 Panasonic ...
Page 40: ...Specifications 28 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Page 134: ...Field Setting 122 Test Operation Urban Multi ML5 Mini UM Heat Pump ...
Page 235: ...Piping Diagrams Appendix 223 U 4 5 6ML5DPQ 3D052712 Panasonic ...
Page 238: ...Piping Diagrams 226 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 240: ...Wiring Diagrams 228 Appendix U 4 5 6ML5DPQ 3D05811B Urban Multi ML5 Mini UM Heat Pump ...
Page 241: ...Wiring Diagrams Appendix 229 2 2 Field Wiring U 4 5 6ML5XPQ 3D057919 Panasonic ...
Page 242: ...Wiring Diagrams 230 Appendix U 4 5 6ML5DPQ 3D052597 Urban Multi ML5 Mini UM Heat Pump ...
Page 243: ...Wiring Diagrams Appendix 231 2 3 Indoor Unit S 20 25 32 63LM3HPQ Panasonic ...
Page 244: ...Wiring Diagrams 232 Appendix S 40 50 80 125LM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 245: ...Wiring Diagrams Appendix 233 S 20 25 32 40 50 63 80 100 125UM4JPQ Panasonic ...
Page 246: ...Wiring Diagrams 234 Appendix S 20 25 32 40 50YM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 247: ...Wiring Diagrams Appendix 235 S 25 32 40 63DM3HPS 3D039564C Panasonic ...
Page 248: ...Wiring Diagrams 236 Appendix S 20 25NM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 249: ...Wiring Diagrams Appendix 237 S 20 25 32 40 50 63FM3HPQ Panasonic ...
Page 250: ...Wiring Diagrams 238 Appendix S80 100 125FM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 252: ...Wiring Diagrams 240 Appendix S 32 63 100TM3JPR 3D039801D Urban Multi ML5 Mini UM Heat Pump ...
Page 255: ...Wiring Diagrams Appendix 243 Panasonic ...
Page 256: ...Wiring Diagrams 244 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 257: ...Wiring Diagrams Appendix 245 Panasonic ...
Page 259: ...Option List Appendix 247 Panasonic ...
Page 262: ...Example of Connection 250 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 283: ......