Troubleshooting by Indication on the Remote Controller
148
Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Provide 220~240V power
supply.
YES
NO
Is power supply
220~240V provided?
Replace the limit switch
connecting cable.
Replace indoor unit PC board.
Replace the power supply
connecting cable.
Replace swing motor.
Take the cam mechanism
apart, reassemble and turn on
again.
YES
NO
YES
YES
NO
YES
NO
Connect the connector to X9A
and turn on again.
Replace indoor unit PC board.
NO
NO
YES
NO
YES
NO
YES
YES
NO
Indoor unit
is a model equipped
with a swing flap
function
The swing
motor works when
the power supply is turned
off and then back
on.
When
the air flow
direction flap's cam
mechanism is disconnected
from the swing motor,
operation is normal
when turned
on again.
The connecting cable
has no continuity.
After
turning
the swing-flap
ON and then stopping
with the remote controller,
the voltage of X6A (or X29A) of
the indoor unit PC board is 220 ~ 240
VAC (50 Hz) / 220 VAC
(60 Hz) when turned on
again (within 30
seconds of
turning on
again).
The connector
is connected to X9A (or X15A) of
the indoor unit PC
board.
The limit switch
functions normally.
The connecting
cable is short-circuited
or disconnected.
Replace swing motor.
(V2780)
Urban Multi ML5 · Mini UM · Heat Pump
Summary of Contents for U-4..6ML5XPQ
Page 1: ...Service Manual U 4 6ML5XPQ DPQ Urban Multi Mini UM Heat Pump ...
Page 2: ......
Page 12: ...Introduction x Urban Multi ML5 Mini UM Heat Pump ...
Page 37: ...Specifications Specifications 25 Panasonic ...
Page 38: ...Specifications 26 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Page 39: ...Specifications Specifications 27 Panasonic ...
Page 40: ...Specifications 28 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Page 134: ...Field Setting 122 Test Operation Urban Multi ML5 Mini UM Heat Pump ...
Page 235: ...Piping Diagrams Appendix 223 U 4 5 6ML5DPQ 3D052712 Panasonic ...
Page 238: ...Piping Diagrams 226 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 240: ...Wiring Diagrams 228 Appendix U 4 5 6ML5DPQ 3D05811B Urban Multi ML5 Mini UM Heat Pump ...
Page 241: ...Wiring Diagrams Appendix 229 2 2 Field Wiring U 4 5 6ML5XPQ 3D057919 Panasonic ...
Page 242: ...Wiring Diagrams 230 Appendix U 4 5 6ML5DPQ 3D052597 Urban Multi ML5 Mini UM Heat Pump ...
Page 243: ...Wiring Diagrams Appendix 231 2 3 Indoor Unit S 20 25 32 63LM3HPQ Panasonic ...
Page 244: ...Wiring Diagrams 232 Appendix S 40 50 80 125LM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 245: ...Wiring Diagrams Appendix 233 S 20 25 32 40 50 63 80 100 125UM4JPQ Panasonic ...
Page 246: ...Wiring Diagrams 234 Appendix S 20 25 32 40 50YM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 247: ...Wiring Diagrams Appendix 235 S 25 32 40 63DM3HPS 3D039564C Panasonic ...
Page 248: ...Wiring Diagrams 236 Appendix S 20 25NM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 249: ...Wiring Diagrams Appendix 237 S 20 25 32 40 50 63FM3HPQ Panasonic ...
Page 250: ...Wiring Diagrams 238 Appendix S80 100 125FM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 252: ...Wiring Diagrams 240 Appendix S 32 63 100TM3JPR 3D039801D Urban Multi ML5 Mini UM Heat Pump ...
Page 255: ...Wiring Diagrams Appendix 243 Panasonic ...
Page 256: ...Wiring Diagrams 244 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 257: ...Wiring Diagrams Appendix 245 Panasonic ...
Page 259: ...Option List Appendix 247 Panasonic ...
Page 262: ...Example of Connection 250 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 283: ......