Field Setting
Test Operation
93
3.1.6 Detailed Explanation of Setting Modes
(1)
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
(2) Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
(3) Selection of Thermistor
Select the thermistor to control room temperature.
The factory setting for the Second Code No. is "01" and room temperature is controlled by the
indoor unit suction air thermistor and remote controller thermistor.
When the Second Code No. is set to "02", room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the remote
controller thermistor.
(4) "Filter Cleaning" Displayed or Not Displayed
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
Filter Specs.
Setting
Standard
Long Life
Ultra Long Life Filter
Contamination Light
200 hrs.
2,500 hrs.
10,000 hrs.
Contamination Heavy
100 hrs.
1,250 hrs.
5,000 hrs.
Mode No.
Setting Switch No.
Setting Position No.
Setting
10 (20)
1
01
Long-Life Filter
02
Ultra-Long-Life Filter (1)
03
—
Mode No.
First Code No.
Second Code No. Thermistor that controls room temperature
10 (20)
2
01
Indoor air thermistor for remote controller
and suction air thermistor for indoor unit
02
Suction air thermistor for indoor unit
03
Thermistor for remote controller
Mode No.
First Code No.
Second Code No.
"Filter Cleaning" display
10 (20)
3
01
Display
02
No display
Panasonic
Summary of Contents for U-4..6ML5XPQ
Page 1: ...Service Manual U 4 6ML5XPQ DPQ Urban Multi Mini UM Heat Pump ...
Page 2: ......
Page 12: ...Introduction x Urban Multi ML5 Mini UM Heat Pump ...
Page 37: ...Specifications Specifications 25 Panasonic ...
Page 38: ...Specifications 26 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Page 39: ...Specifications Specifications 27 Panasonic ...
Page 40: ...Specifications 28 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Page 134: ...Field Setting 122 Test Operation Urban Multi ML5 Mini UM Heat Pump ...
Page 235: ...Piping Diagrams Appendix 223 U 4 5 6ML5DPQ 3D052712 Panasonic ...
Page 238: ...Piping Diagrams 226 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 240: ...Wiring Diagrams 228 Appendix U 4 5 6ML5DPQ 3D05811B Urban Multi ML5 Mini UM Heat Pump ...
Page 241: ...Wiring Diagrams Appendix 229 2 2 Field Wiring U 4 5 6ML5XPQ 3D057919 Panasonic ...
Page 242: ...Wiring Diagrams 230 Appendix U 4 5 6ML5DPQ 3D052597 Urban Multi ML5 Mini UM Heat Pump ...
Page 243: ...Wiring Diagrams Appendix 231 2 3 Indoor Unit S 20 25 32 63LM3HPQ Panasonic ...
Page 244: ...Wiring Diagrams 232 Appendix S 40 50 80 125LM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 245: ...Wiring Diagrams Appendix 233 S 20 25 32 40 50 63 80 100 125UM4JPQ Panasonic ...
Page 246: ...Wiring Diagrams 234 Appendix S 20 25 32 40 50YM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 247: ...Wiring Diagrams Appendix 235 S 25 32 40 63DM3HPS 3D039564C Panasonic ...
Page 248: ...Wiring Diagrams 236 Appendix S 20 25NM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 249: ...Wiring Diagrams Appendix 237 S 20 25 32 40 50 63FM3HPQ Panasonic ...
Page 250: ...Wiring Diagrams 238 Appendix S80 100 125FM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Page 252: ...Wiring Diagrams 240 Appendix S 32 63 100TM3JPR 3D039801D Urban Multi ML5 Mini UM Heat Pump ...
Page 255: ...Wiring Diagrams Appendix 243 Panasonic ...
Page 256: ...Wiring Diagrams 244 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 257: ...Wiring Diagrams Appendix 245 Panasonic ...
Page 259: ...Option List Appendix 247 Panasonic ...
Page 262: ...Example of Connection 250 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Page 283: ......