Wiring
© Panasonic Industrial Devices SUNX Co., Ltd. 2017
60
2-5-5 Wiring for Manual Reset (Interlock is Valid)
(Example of Control Category 4 Wiring)
This is a common connection method whereby one emitter and one receiver face each other.
The control output (OSSD 1 / 2) turns OFF when light is blocked.
●
Using line synchronization setting and 8-core cable
<Using PNP output>
Emitter
Receiver
K1
K2
+
24V DC
+20
-30
%
−
Gray cable
Gray cable
(with black line)
(Brown) +V
(Brown) +V
(Pale purple) Interlock setting input
(Pink) Test / Reset input
(Red) Auxiliary output
(Pale blue) Output polarity setting / Lockout release input
(Pale blue) Output polarity setting / Lockout release input
(Blue) 0V
(Blue) 0V
(Orange) Synchroni
(Pale purple) External device monitor input
(Black) Control output 1 (OSSD 1)
(White) Control output 2 (OSSD 2)
(Orange) Synchroni
(Orange / Black) Synchronization -
(Orange / Black) Synchronization -
*S1
Interlock function
Valid (manual reset)
External device monitor function Invalid
Auxiliary output
Not possible
*Symbols
Switch S1
Vs to Vs − 2.5V (sink current 5mA or less): Emission halt (Note 1), Open: Emission
K1, K2: Safety relay unit, etc.
Notes: 1) Vs is the supply voltage.
2) For information on reset, refer to
“3-2 Interlock Function (8-core cable, 12-core cable)”
.
Summary of Contents for SF4D Series
Page 2: ... Panasonic Industrial Devices SUNX Co Ltd 2017 2 MEMO ...
Page 126: ...Functions Panasonic Industrial Devices SUNX Co Ltd 2017 126 MEMO ...
Page 130: ...Maintenance Panasonic Industrial Devices SUNX Co Ltd 2017 130 MEMO ...
Page 140: ...Troubleshooting Panasonic Industrial Devices SUNX Co Ltd 2017 140 MEMO ...
Page 174: ... Panasonic Industrial Devices SUNX Co Ltd 2017 174 MEMO ...