25.2.39 Outdoor Pipe Temperature Sensor Abnormality (H28 / F06 / F42)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
Is the measured resistance of the outdoor heat exchanger
temperature sensor matches the value specified in its
characteristic chart?
When abnormality indication starts again
Check the outdoor heat exchanger temperature sensor:
●
Plug out connector from the outdoor unit PCB
●
Measure the resistance of the outdoor heat exchanger
temperature sensor
●
Defect in outdoor heat exchanger
temperature sensor
●
Replace the outdoor heat exchanger
temperature sensor
●
Defect in outdoor unit PCB
●
Replace the outdoor unit PCB
Check the connector connection:
●
Turn off the power
●
Check the connector connection
Is the connector connection normal?
●
Connector poor contact
●
Correct the connection
YES
Sensor (Thermistor)
Characteristics
70
60
50
40
30
20
10
0
1
2
Outdoor Air Sensor
Outdoor Heat Exchanger
Sensor
1
2
-10
0
10
20
30
40
50
Temperature (°C)
R
e
si
st
a
n
ce
(
kΩ
)
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
NO
NO
YES
Caution