246
Diagnosis
display
(Indoor
model:
CS-XX /
S-XX /
WH-XX)
Abnormality
or
protection
control
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
Abnormality
judgement
Protection
operation
Problem
Check location
F93 / P29 /
F14
Compressor
abnormal
revolution
○
○
○
4 times
happen
within 20
minutes
-
Compressor
abnormal
revolution
Power transistor
module faulty or
compressor lock
F94 / P04 /
F12
Compressor
discharge
pressure
overshoot
protection
○
○
4 times
happen
within 30
minutes
-
Compressor
discharge
pressure
overshoot
Check
refrigeration
system
F95 / P04 /
F95
Outdoor cooling
high pressure
protection
○
○
○
4 times
happen
within 20
minutes
-
Cooling high
pressure
protection
Check
refrigeration
system
Outdoor air
circuit
F96 / P07 /
F22
Power transistor
module
overheating
protection
○
○
○
4 times
happen
within 30
minutes
-
Power transistor
module overheat
PCB faulty
Outdoor air
circuit (fan
motor)
F97 / P03 /
F20
Compressor
overheating
protection
○
○
○
○
3 times
happen
within 30
minutes
-
Compressor
overheat
Insufficient
refrigerant
F98 / H01 /
F16
Total running
current protection
○
○
3 times
happen
within 20
minutes
-
Total current
protection
Check
refrigeration
system
Power source or
compressor lock
F99 / P16 /
F23
Outdoor direct
current (DC) peak
detection
○
○
○
Continuous
happen for
7 times
-
Power transistor
module current
protection
Power transistor
module faulty or
compressor lock
LED 1 illuminate is indicated that outdoor unit is operating normally. If the LED 1 is switched off or flashing, check the power supply and
self-diagnosis indication.
●
------ Illuminate
○
------ Flashing
Blank ------ OFF