12.1.10.2 Operating the High-spec Wired
Remote Controller (CZ-RTC5B)
20:30 (THU)
START
[ ]
How to set the external static pressure
1. Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
20:30 (THU)
2. Press the
or
button to see each menu.
If you wish to see the next screen instantly, press
the
or
button. Select “8. Detailed
settings” on the LCD display and press the
button.
20:30 (THU)
The “Detailed settings” screen appears on the
LCD display.
Select the “Unit no.” by pressing the
or
button for changes.
Detailed settings
Unit no. Code no. Set data
10
Sel. Next
20:30 (THU)
3. Select the “Code no.” by pressing the
or
button.
Change the “Code no.” to “B0” by pressing the
or
button (or keeping it pressed).
Detailed settings
Unit no. Code no. Set data
1-1
-001
Sel. Next
20:30 (THU)
B0
4. Select the “Set data” by pressing the
or
button.
Select one of the “Set data” among “0001” –
“0010” according to the desired external static
pressure setting by pressing the
or
button.
Then press the
button.
(See the table below.)
When setting to auto airflow volume control:
Select the setting data to “-002”.
Then press the
button.
Table 10-2 Setting the external static pressure
Indoor unit type
Item code
S-71WF3E
B0
Outdoor unit type
CU-2WZ71YBE5
External static pressure of the rated airflow
volume (Pa)
150
0010
140
0009
130
0008
120
0007
110
0006
90
0005
70
0004
50
0003
30 *
0002
10
0001
No auto airflow volume setting
-001
Auto airflow volume setting
-002
* Setting at shipment