166
13.2 Select The Best Location
13.2.1 Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
Refrigerant piping size
Outdoor Unit
CU-2WZ71****
Liquid - side
ø 6.35 t0.8
Gas - side
ø 12.7 t0.8
•
This illustration is for explanation purposes only.
1/2" Gas side piping ( )
1/4" Liquid side piping ( )
Additional drain hose ( )
Connection cable ( )
(To Tank and Duct unit)
Outdoor Unit Installation Diagram
Installation parts you
should purchase ( )
*
Note:
Respective indoor unit installation procedure shall
refer to instruction manual provided in the indoor unit
packaging.
It is advisable to avoid
more than 2 blockage
directions. For better
ventilation & multiple-
outdoor installation,
please consult
authorized dealer/
specialist.
Refrigerant Amount and Allowable Piping Length
Outdoor Unit
CU-2WZ71****
Pre-charged refrigerant
2.4 k
g
Maximum total piping length for additional gas
30 m
Additional refrigerant
20
g
/m
Rated length (m)
Indoor - Duct unit
5 m
Indoor - Tank unit
5 m
Allowable piping length of each indoor unit (min-max)
3 m ~ 35 m
Allowable total piping length of all indoor unit
70 m or less
Height difference between indoor and outdoor unit
Outdoor unit located on upper side
30 m or less
Outdoor unit located otherwise
15 m or less
Height difference between indoor and outdoor unit
Outdoor unit located on upper side
15 m or less
Outdoor unit located otherwise
30 m or less