![Panasonic S-71WF3E Service Manual Download Page 259](http://html.mh-extra.com/html/panasonic/s-71wf3e/s-71wf3e_service-manual_1507724259.webp)
259
25.2.13 Abnormal External Thermistor 1 (- / - / H67)
Malfunction Caused:
1 Faulty connector connection.
2 Faulty room temperature zone 1 sensor.
3 Faulty indoor sub PCB.
Abnormality Judgment:
Continue for 5 seconds.
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
YES
●
Correct connection
NO
●
Change external thermistor 1
NO
YES
Disconnect sensor from sub PCB measure resistance of sensor
and compare against sensor characteristic same?
Abnormal external thermistor 1
Check CN205 connector on sub PCB normal?
Change sub PCB
Caution