1
- 7
2WAY SYSTEM
Control Functions-Outdoor Unit
1
3. Compressor Control
*The evaporation temperature area changes depending on the maximum required level of each indoor unit as
shown in the right figure.
*C area is regarded as B area for 6 minutes after compressor starts.
*When the system operates in a minimum capacity, the system will continue operating for at least 6 minutes if the
evaporation temperature area is C area.
*The evaporation temperature is not adjusted while specially controlling defrosting and the oil recovery, etc.
*The evaporation temperature is not adjusted when there are one or more indoor units that select the test run.
If one or more indoor units are selected into test run, the system doesn't stop in all states except alarm appearing.
*The test run will finish automatically in about one hour.
Compressor capacity can increase
5.5
Te_tgt_max.
Compressor capacity
cannot increase
Compressor capacity decreases
Max. required level
15
0
5.0
2.0
deg
1.5
Te_tgt_min.
5.0
2.0
15.0
12.0
30
10.0
7.0
B area
C area
A area
Evaporation temperature area
B area is able to shift by EEPROM setting of outdoor unit.
EEPROM setting in main outdoor unit
Area shift function
Lower temperature of B area
= 2.0 + Te_L
CODE: 3F
Setting No
Te_L (deg)
-9
-8
Interval of “1”
-1
0 (factory preset mode)
0
1
-9
-8
-1
1
9
9
C area shifts according to changed Te_L
Lower temperature of B area
= 5.0 + Te_U
CODE: 40
Setting No
Te_U (deg)
-9
-8
Interval of “1”
-1
0 (factory preset mode)
0
1
9
-9
-8
-1
1
9
A area shifts according to changed Te_H