1
- 25
2WAY SYSTEM
Control Functions-Outdoor Unit
1
7. Oil Control
* It is possible to change the oil recovery control processing time
EEPROM setting in main outdoor unit
CODE: 43
* There is no stop time before and after defrosting operation in factory setting.
However, it is possible to stop by setting.
EEPROM setting in main outdoor unit
CODE: F4 (Time before oil recovery 1)
F5 (Time before oil recovery 2)
F6 (Time after oil recovery 1)
F7 (Time after oil recovery 2)
7-6. Indoor unit self oil recovery control
This control is carried out regularly when the system is in cooling mode.
-During stopped, fan or thermostat OFF condition, indoor unit expansion valve is opened regularly for 1 to 2 min-
utes regularly (at an interval of once every 2 hours.)
-During the thermostat ON, the indoor unit electronic thermostatic expansion valve is opened about 10 pulses
from the current status.
The state of the indoor unit is shown in the table below. Type K1 operates differently according to the setting.
EEPROM setting in main outdoor unit
CODE: 24
Setting No. 0
Setting No. 1
Type of
indoor unit
Mode of
indoor unit
Thermostat
ON/OFF
Pulse of MOV
Fan speed Flap
Fan speed Flap
K1
Stop
-
100 - 180
Stop
-
LL
Close
Fan (only)
-
100 - 180
LL
-
LL
Close
Cooling
OFF
115 - 185
Set speed -
Set speed -
ON
Present pulse + 20
Set speed -
Set speed -
Excluding
K1, E1
Stop
-
100 - 180
Stop
-
Stop
-
Fan (only)
-
100 - 180
Stop
-
Stop
-
Cooling
OFF
115 - 185
Set speed -
Set speed -
ON
Present pulse + 20
Set speed -
Set speed -
E1
Stop
-
100 - 180
Stop
-
Stop
-
Fan mode
-
100 - 180
LL
-
LL
-
Cooling
OFF
115 - 185
Set speed -
Set speed -
ON
Present pulse + 20
Set speed -
Set speed -
*MOV pulse might be a little different from the above values according to the operating condition.
Setting No
Oil recovery control processing time
0
30
60
0 seconds
30 seconds
60 seconds (factory preset mode)
Interval of “30”
570
600
570 seconds
600 seconds
Setting No
Time above mention
-1
0
30
60
Non stop (factory preset mode)
0 seconds
30 seconds
60 seconds
Interval of “30”
570
570 seconds
600
600 seconds