2WAY SYSTEM
Control Functions
-
Outdoor Unit
1
- 8
1
3. Compressor Control
Condensation temperature area at cooling operation
3-6-2. Condensation temperature adjustment by roadmap control
Target temperature of the B area is different between cooling and heating operation.
Target lower temperature
(Tc_tgt_min)
Target upper temperature
(Tc_tgt_max)
Cooling
53.0
℃
55.0
℃
Heating
48.0
℃
51.0
℃
-Cooling operation
The purpose of this control at cooling is to prevent abnormal high-pressure.
Compressor capacity can increase
Compressor capacity cannot increase
Thermostat OFF
Compressor capacity decreases
Tc_tgt_max.
Tc_tgt_min.
deg
B area
A area
C area
- Heating operation
The heating capacity is adjusted with this control. It also prevents abnormal high-pressure.
Condensation temperature area at heating operation
Compressor capacity can increase
Compressor capacity holds
Thermostat OFF
Compressor capacity decreases
Tc_tgt_max.
Tc_tgt_min.
deg
B area
A area
C area
*PX is usually fixed to 58deg. If the high pressure goes up rapidly after the compressor starts, the system
experiences urgent stop. The next time the system will start with lower PX.
*In the B area, the compressor capacity changes depending on the refrigerant condition.
*When the system operates in a minimum capacity, the system will continue operating for at least 6 minutes if the
condensation temperature area is C area.
*The condensation temperature is not adjusted when there are one or more indoor units that select the test run.