1
- 43
2WAY SYSTEM
Control Functions-Outdoor Unit
1
DN
Item
Setting No
30
System oil recovery in regular intervals
0(P)=Valid, 1=Cancel (For detail refer to 7-5-1),
2=No use
31
Factory use
-
32
Invalid
-
34
Invalid
-
35
Condensation temperature adjustment
Lower temperature of B area (Tc_L)
-7, -6,,, ,,, 0(P),,, ,,, 6, 7
(For detail refer to 3-6-2)
36
Condensation temperature adjustment
Upper temperature of B area (Tc_U)
-7, -6,,, ,,, 0(P),,, ,,, 6, 7
(For detail refer to 3-6-2)
38
Factory use
-
39
Aid capacity of compressor adjustment
(Additional compressor capacity at part load)
-2, -1, 0(P), 1, 2 (House power)
3A
Factory use
-
3B
Factory use
-
3C
Minimum horse power of compressor in cooling
0(P)=0.1, 1=0.1, 2=0.2,,, ,,,99=9.9
3D
Minimum horse power of compressor in heating
0(P)=0.1, 1=0.1, 2=0.2,,, ,,,99=9.9
3E Delay start of outdoor unit
0(P), 1, 2, 3 (For detail refer to 2-2-2)
3F
Evaporation temperature adjustment
Lower temperature of B area (Te_L)
-9, -8,,, ,,, 0(P),,, ,,, 8, 9
(For detail refer to 3-6-1)
40
Evaporation temperature adjustment
Upper temperature of B area (Te_U)
-9, -8,,, ,,, 0(P),,, ,,, 8, 9
(For detail refer to 3-6-1)
41
Regular intervals of system oil recovery control
(Long operation time in the part load)
30, 40,,, ,,, 150(P),,, ,,,290, 300
(For detail refer to 7-5)
43
Oil recovery control processing time
0, 30, 60(P), 90,,, ,,, 570, 600 (For detail refer to 7-5-2)
46
Factory use
-
47
Factory use
-
48
Automatic backup operation
0(P)=Valid, 1=invalid
49
Factory use
-
4A Forced defrosting (SILENT pin action)
0(P)=Silent mode, 1=Forced defrosting
4B Limit pressure adjustment
0, 1, 2(P), 3 (For detail refer to 3-6-2)
4C
Factory use
-
4D
Interval of system oil recovery control
0=0, 1=15, 2=30(P), 3=45, 4=60 (For detail refer to
7-5)
4E
Upper current limitation mode
invalid at defrosting
0(P), 1
4F
Factory use
-
60 –75: Memory area for production
DN
Item
Setting No
60
|
75
For production