1-3
1
1
Single-Type
High Static Pressure Ducted Type S-250PE2E5 / U-250PE2E8A
INDOOR
MODEL
S-250PE2E5
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-250PE2E8A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253 / EN14511 / EN12102
Power supply
Ø, Hz
1Ø 50Hz
3Ø 50Hz
V
220V
230V
240V
380V
400V
415V
Min
Max
C
O
O
L
I
N
G
Capacity
kW
25.0
25.0
25.0
-
-
-
6.3
28.0
BTU/h
85300
85300
85300
-
-
-
21500
95500
Current
A
3.30
3.20
3.10
13.0
12.5
12.0
-
-
Input power
W
560
560
560
8.040k
8.040k
8.040k
-
-
TOTAL W
-
8.600k
8.600k
8.600k
-
-
Annual consumption
TOTAL kWh *4
-
-
-
-
4300
-
-
-
EER/EER CLASS
TOTAL (W/W) *5 / ("A"~"G")
-
-
-
2.91
2.91/C
2.91
-
-
Erp
*6
Pdesign
kW
-
-
-
-
-
-
-
-
SEER
(W/W)
-
-
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
94
93
93
-
-
Noise indoor
dB-A (H/M/L)
47/45/42
-
-
-
Power Level dB
79/77/74
-
-
-
Noise outdoor
dB-A (H/L)
-
61/-
-
-
Power Level dB
-
80/-
-
-
H
E
A
T
I
N
G
Capacity
kW
28.0
28.0
28.0
-
-
-
7.1
31.5
BTU/h
95500
95500
95500
-
-
-
24200
107500
Current
A
3.30
3.20
3.10
11.5
11.1
10.7
-
-
Input power
W
560
560
560
7.140k
7.140k
7.140k
-
-
TOTAL W
-
7.700k
7.700k
7.700k
-
-
COP/COP CLASS
TOTAL (W/W) *5/ ("A"~"G")
-
-
-
3.64
3.64/A
3.64
-
-
Erp
*6
Pdesign at -10°C
kW
-
-
-
-
-
-
-
-
Tbivalent
°C
-
-
-
-
-
-
-
-
SCOP
(W/W)
-
-
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
94
93
93
-
-
Noise indoor
dB-A (H/M/L)
47/45/42
-
-
-
Power Level dB
79/77/74
-
-
-
Noise outdoor
dB-A (H/L)
-
63/-
-
-
Power Level dB
-
82/-
-
-
EXTRA LOW TEMP Total capacity(kW)/Input power(W)/COP
-
-
Max Current(A) / Max Input power(W)
7.30/1.66k
7.30/1.74k
7.30/1.81k
20.0/12.4k
20.0/12.9k
20.0/13.4k
-
Startring current(A) / Comp output(W)
-
-
-
13.0/5.5k
12.5/5.5k
12.0/5.5k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
750
120 × 2
-
Moisture removal volume
L/h(Pt/h)
13.9 (29.2)
-
-
External static pressure
Pa
72 / (140/270)
-
-
Indoor
Air flow
Cooling
m
3
/min (m
3
/h) (H/M/L)
72/63/53 (4320/3780/3180)
-
-
-
Heating
m
3
/min (m
3
/h) (H/M/L)
72/63/53 (4320/3780/3180)
-
-
-
Outdoor
Air flow
Cooling
m
3
/min (m
3
/h)
-
160 (9600)
-
-
Heating
m
3
/min (m
3
/h)
-
160 (9600)
-
-
Refrigerrant type / amount
g
(oz)
-
R410A 6.4k (225.8)
-
Product dimension
Height mm(inch)
479 (18-27/32)
1500 (59-1/16)
-
Width mm(inch)
1453 (57-7/32)
980 (38-37/64)
-
Depth mm(inch)
1205 (47-7/16)
370 (14-9/16)
-
Packing dimension
Height mm(inch)
614 (24-3/16)
1642 (64-41/64)
-
Width mm(inch)
1536 (60-15/32)
1095 (43-7/64)
-
Depth mm(inch)
1339 (52-23/32)
529 (20-53/64)
-
Weight
(NET) k
g
(lb)
104 (230)
138 (304)
-
(GROSS) k
g
(lb)
136 (300)
150 (331)
-
Layers limit (actually)
4 (5)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø12.7(1/2) (Gas)Ø25.4(1)
(Liquid)Ø12.7(1/2) (Gas)Ø25.4(1)
-
Connecting method, Standard length m (ft)
(Liquid)flared type (Gas)brazing connection, 7.5(24.6) (Liquid)flared type (Gas)brazing connection, 7.5(24.6)
-
Pipe length range m (ft)
5~120m (16.4~393.7)
-
Indoor unit & Outdoor unit height difference m (ft)
30m(Outdoor unit located lower)/30m(Outdoor unit located higher) (98.4/98.4)
-
Add gas amount
g
/m (oz/ft)
(Liquid)Ø12.7(1/2): 80
g
(0.860)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
SM830252-01_欧州_Single_8・10HP_TD_SM.indb 3
16/10/14 13:57:04
AMP Air Conditioning
www.ampair.co.uk | [email protected]