7
7
Item
code
Item
Setting data
No.
Description
No.
Description
No.
Description
Type
0000
0001
0002
0003
0005
0006 High Static Pressure
Ducted (E2)
0007
0008
0010
0011
Indoor unit
capacity
0001
0003
0005
0007
0009
0011
0012
0015
0017
0020
0021
224 (Type 200)
4-Way Cassette (U2)
112 (Type 100)
140 (Type 125)
0023
280 (Type 250)
System
address
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0030 Unit No. 30
0099 Not set
Indoor unit
address
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0064 Unit No. 64
0099 Not set
Group control
address
0000 Individual (1:1 = Indoor unit with no group wiring)
0001 Main unit (One of the group-control indoor units)
0002 Sub unit (All group-control indoor units except for main unit)
0099 Not set
Cooling intake
temperature
shift
–010 Shifts intake temperature 10°C down.
–009 Shifts intake temperature 9°C down.
–001 Shifts intake temperature 1°C down.
0000 No intake temperature shift
0001 Shifts intake temperature 1°C up.
0009 Shifts intake temperature 9°C up.
0010 Shifts intake temperature 10°C up.
Automatic
stop time after
operation start
0000 Function disabled
0001 Stops automatically 5 minutes after operation starts.
0002 Stops automatically 10 minutes after operation starts.
Can be set
in 5-minute
units.
*
0123 Stops automatically 615 minutes after operation starts.
0124 Stops automatically 620 minutes after operation starts.
0125 Stops automatically 625 minutes after operation starts.
7-4. List of Detailed Setting Items
<Procedure of CZ-RTC5A>
Fig. 7-4
START
[ ]
20:30 (THU)
CZ-RTC5A
1 Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2 Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “8. Detailed settings” on the LCD display
and press the
button.
The “Detailed settings” screen appears on the
LCD display.
Select the “Unit no.” by pressing the
or
button for changes.
3 Select the “Code no.” by pressing the
or
button.
Change the “Code no.” by pressing the
or
button (or keeping it pressed).
4 Select the “Set data” by pressing the
or
button.
Select one of the “Set data” by pressing the
or
button.
Then press the
button.
5 Select the “Unit no.” by pressing the
or
button and press the
button.
The “Exit detailed settings and restart?” (Detailed
setting-end) screen appears on the LCD display.
Select “YES” and press the
button.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Detailed settings
Unit no.
Code no.
Set data
10
3-1
0001
Sel.
Next
20:30 (THU)
Detailed settings
Unit no.
Code no.
Set data
3-1
0001
Sel.
Next
20:30 (THU)
10
Detailed settings
Unit no.
Code no.
Set data
3-1
Sel.
20:30 (THU)
10
0001
[
]
Confirm
Detailed settings
Unit no.
Code no.
Set data
ALL
Sel.
Next
20:30 (THU)
01
0002
Exit detailed settings
and restart?
NO
YES
SM830255-00_Single_欧州4方向 TD&SM.indb 7
16/09/21 13:54:48
7-7
SM830252-01_欧州_Single_8・10HP_TD_SM.indb 7
16/10/13 11:02:01
AMP Air Conditioning
www.ampair.co.uk | [email protected]