1-4
1
1
Twin-Type
4-Way Cassette Type S-100PU2E5A ×2 / U-200PE2E8A
INDOOR
MODEL
S-100PU2E5A×2
-
-
PANEL
MODEL
Standard type: CZ-KPU3 / ECONAVI type: CZ-KPU3A
-
-
OUTDOOR
MODEL
-
U-200PE2E8A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151 / EN14511 / EN12102
Power supply
Ø, Hz
1Ø 50Hz
3Ø 50Hz
V
220V
230V
240V
380V
400V
415V
Min
Max
C
O
O
L
I
N
G
Capacity
kW
20.0
20.0
20.0
-
-
-
5.4
22.4
BTU/h
68200
68200
68200
-
-
-
18400
76400
Current
A
0.82 ×2
0.79 ×2
0.76 ×2
9.70
9.30
9.00
-
-
Input power
W
100 ×2
100 ×2
100 ×2
5.940k
5.940k
5.940k
-
-
TOTAL W
-
6.040k
6.040k
6.040k
-
-
Annual consumption
TOTAL kWh *4
-
-
-
-
3020
-
-
-
EER/EER CLASS
TOTAL (W/W) *5 / ("A"~"G")
-
-
-
3.31
3.31/A
3.31
-
-
Erp
*6
Pdesign
kW
-
-
-
-
-
-
-
-
SEER
(W/W)
-
-
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
93
92
92
-
-
Noise indoor
dB-A (H/M/L) *7
45/38/32
-
-
-
Power Level dB
60/53/47
-
-
-
Noise outdoor
dB-A (H/L)
-
60/-
-
-
Power Level dB
-
78/-
-
-
H
E
A
T
I
N
G
Capacity
kW
22.4
22.4
22.4
-
-
-
5.6
25.0
BTU/h
76400
76400
76400
-
-
-
19100
85300
Current
A
0.81 ×2
0.78 ×2
0.75 ×2
8.55
8.20
7.90
-
-
Input power
W
95 ×2
95 ×2
95 ×2
5.165k
5.165k
5.165k
-
-
TOTAL W
-
5.260k
5.260k
5.260k
-
-
COP/COP CLASS
TOTAL (W/W) *5/ ("A"~"G")
-
-
-
4.26
4.26/A
4.26
-
-
Erp
*6
Pdesign at -10°C
kW
-
-
-
-
-
-
-
-
Tbivalent
°C
-
-
-
-
-
-
-
-
SCOP
(W/W)
-
-
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
92
91
91
-
-
Noise indoor
dB-A (H/M/L) *7
45/38/32
-
-
-
Power Level dB
60/53/47
-
-
-
Noise outdoor
dB-A (H/L)
-
62/-
-
-
Power Level dB
-
80/-
-
-
EXTRA LOW TEMP Total capacity(kW)/Input power(W)/COP
-
-
Max Current(A) / Max Input power(W)
0.82 ×2/ 100 ×2 0.79 ×2/ 100 ×2 0.76 ×2/ 100 x2 20.0/12.2k
20.0/12.8k
20.0/13.2k
-
Startring current(A) / Comp output(W)
-
-
-
9.70/4.2k
9.30/4.2k
9.0/4.2k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
90
120 × 2
-
Moisture removal volume
L/h(Pt/h)
5.4 (2.7×2) (11.3)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *7
Cooling
m
3
/min (m
3
/h) (H/M/L)
36/26/18×2 (2160/1560/1080 ×2)
-
-
-
Heating
m
3
/min (m
3
/h) (H/M/L)
36/26/18×2 (2160/1560/1080 ×2)
-
-
-
Outdoor
Air flow
Cooling
m
3
/min (m
3
/h)
-
164 (9840)
-
-
Heating
m
3
/min (m
3
/h)
-
164 (9840)
-
-
Refrigerrant type / amount
g
(oz)
-
R410A 5.60k (197.5)
-
Product dimension
Height mm(inch)
319 (12-9/16)
1500 (59-1/16)
-
Width mm(inch)
840 (33-5/64)
980 (38-37/64)
-
Depth mm(inch)
840 (33-5/64)
370 (14-9/16)
-
Product dimension (Panel) H×W×D mm(inch) 33.5×950×950 (1-11/32 × 37-13/32 × 37-13/32)
-
-
Packing dimension
Height mm(inch)
365 (14-3/8)
1642 (64-41/64)
-
Width mm(inch)
898 (35-3/8)
1095 (43-7/64)
-
Depth mm(inch)
898 (35-3/8)
529 (20-53/64)
-
Weight
(NET) k
g
(lb)
25 (55)
127 (280)
-
(GROSS) k
g
(lb)
32 (71)
139 (306)
-
Panel (NET) k
g
(lb)
5 (11)
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø9.52(3/8) (Gas)Ø25.4(1)
-
Connecting method, Standard length m (ft)
flared type, 7.5(24.6)
(Liquid)flared type (Gas)brazing connection, 7.5(24.6)
-
Pipe length range m (ft)
5~120m (16.4~393.7)
-
Indoor unit & Outdoor unit height difference m (ft)
30m(Outdoor unit located lower)/30m(Outdoor unit located higher) (98.4/98.4)
-
Add gas amount
g
/m (oz/ft)
(Liquid)Ø9.52(3/8): 50
g
(0.54)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830252-01_欧州_Single_8・10HP_TD_SM.indb 4