Cooling capacity ratio (maximum capacity)
Heating capacity ratio (maximum capacity)
1-7. Capacity Correction Graph According to Temperature Condition
U-200PE2E8A / U-250PE2E8A (For 50 Hz)
Indoor air intake temp (WB)
22WB
19WB
16WB
22WB
19WB
16WB
Indoor air intake temp (WB)
Outdoor air intake temp (°C DB)
16
°C
20
°C
24
°C
Outdoor air intake temp (°C DB)
24
°C
20
°C
16
°C
1. The graphs " " of the characteristics show the value under the following conditions.
Equivalent tubing length
: 7.5m
Difference of elevation
: 0m
Wind speed
: High
2. " " marking indicates the maximum capacity / maximum power consumption under the JIS condition.
Maximum capacity indicates the maximum value in the parentheses of the specifications (cooling and heating capacity).
3. The characteristic of heating capacity excludes the decline of capacity when frosting (including defrost drive).
NOTE 1
Indoor air intake temp (
°C
WB)
Indoor air intake temp (
°C
WB)
0.88
0.88
0.88
0.88 0.88 0.88 0.88
0.86
0.88
0.83 0.83
0.82
0.82
0.83 0.83
-20 -15 -10 -9
-8
-7
-6
-5
-4
-3
-2
-1
1.0
7
0
1
2
6
5
4
3
0.91 0.95
0.85 0.89
To calculate the heating capacity with consideration for frosting / defrosting operation, multiply the heating
capacity found from the capacity graph by the correction coefficient from the table above.
Outdoor unit heating capacity correction coefficient during of frosting / defrosting
(RH approximately 85%)
Outdoor intake air
temperature
°C WB
Correction coefficient