PAW-VP•LDHW - Technical Manual – 2020-07
How to make Settings
9
!
Important
All settings are necessary, otherwise faultless operation is not possible. Please follow the se-
quence described above!
M
PAW-VP380L – U-200PZH2E8 (PACi R32)
Indoor Unit Tank detailed settings; Remote controller CZ-RTC5B
Parameter
"DN" code
Default
value
New value
to set
Explanation
Check and adjust
10
0006
0031
Unit Type
11
0015
0021
Capacity code
06
0004
0000
Inlet temperature shift in heating mode.
0b
0002
0001
EXCT setting
0C
0000
0001
Heating preparation display
0d
0000
0001
Cool/ Heat auto
15
0022
0022
Temperature sensors
16
0000
0000
Fan speed adjustment
1F
0000
0015
Cooling upper limit 15°C
20
0000
0005
Cooling lower limit 5°C
21
0030
0055
Heating upper limit 55°C
22
0018
0035
Heating lower limit 35°C
28
0001
0001
Automatic restart after power failure activated
2C
0000
0006
Expansion valve setting
2d
0008
0010
Operation mode Cooling and Heating
i
Note
“DN” codes 10 & 11 must be set first.
“DN” 15 display temperature sensor TA, E1, E2, E3*, BL* change 0022 -> 0031
* to be purchased separately
Outdoor unit detailed settings by CZ-RTC2/4
Parameter
"DN" code
Default
value
New value
to set
Explanation
Check and adjust
7
000
001
Specific tank setting
42
002
000
Tank offset
4b
001
001
Specific tank setting
35
000
005
Condensation temperature minimum shift in
heating
36
000
005
Condensation temperature maximum shift in
heating
A5
000
-04
Frost adherence temperature