33
PAW-VP•LDHW - Technical Manual – 2020-07
Performance Characteristic Tables
3
3.1 Capacity tables PAW-VP1000LDHW
3.1.1 Capacity table PAW-VP1000LDHW (10 °C)
City water inlet temp:
10 °C
Outdoor unit type:
U-250PE2E8A
Tank type:
PAW-VP1000LDHW
Ambient
temperature
Water temp
Time
Heating Capacity Power Input
COP
WB
Set temp
[h:m:s]
[kWh]
[kWh]
+25°C
45°C
2:45:41
38.27
11.02
3.47
50°C
3:29:38
44.34
13.94
3.18
55°C
4:15:42
48.38
17.00
2.85
+20°C
45°C
2:51:13
11.39
11.39
3.36
50°C
3:36:38
44.34
14.41
3.08
55°C
4:25:14
48.38
17.57
2.75
+15°C
45°C
2:41:04
38.27
10.71
3.57
50°C
3:23:47
44.34
13.55
3.27
55°C
4:08:34
48.38
16.53
2.93
+12°C
45°C
2:44:23
38.27
10.93
3.50
50°C
3:27:58
44.34
13.83
3.21
55°C
4:13:41
48.38
16.87
2.87
+7°C
45°C
2:41:04
38.27
10.71
3.57
50°C
3:23:47
44.34
13.55
3.27
55°C
4:08:34
48.38
16.53
2.93
+2°C
45°C
3:08:53
38.27
12.56
3.05
50°C
3:58:58
44.34
15.89
2.79
55°C
4:51:29
48.38
19.38
2.50
+0°C
45°C
3:10:40
38.27
12.68
3.02
50°C
4:01:15
44.34
16.04
2.76
55°C
4:54:16
48.38
19.57
2.47
-2°C
45°C
3:09:42
38.27
12.62
3.03
50°C
4:00:01
44.34
15.96
2.78
55°C
4:52:46
48.38
19.47
2.49
-7°C
45°C
3:13:32
38.27
12.87
2.97
50°C
4:04:52
44.34
16.29
2.72
55°C
4:58:41
48.38
19.86
2.44
-10°C
45°C
3:16:45
38.27
13.08
2.92
50°C
4:08:56
44.34
16.55
2.68
55°C
5:03:39
48.38
20.19
2.40
-15°C
45°C
3:22:07
38.27
13.44
2.85
50°C
4:15:43
44.34
17.01
2.61
55°C
5:11:55
48.38
20.74
2.33
-20°C
45°C
3:27:28
38.27
13.80
2.77
50°C
4:22:30
44.34
17.46
2.54
55°C
5:20:11
48.38
21.29
2.27
• Based on peak cut setting 70%
• Please note: The data mentioned in this document is obtained by calculation.
Please use only for reference.
• Equivalent tubing length: 7.5 m, Difference of elevation: 0 m