34
PAW-VP•LDHW - Technical Manual – 2020-07
Performance Characteristic Tables
3
3.1.2 Capacity table PAW-VP1000LDHW (12 °C)
City water inlet temp:
12 °C
Outdoor unit type:
U-250PE2E8A
Tank type:
PAW-VP1000LDHW
Ambient
temperature
Water temp
Time
Heating
Capacity
Power Input
COP
WB
Set temp
[h:m:s]
[kWh]
[kWh]
+25°C
45°C
2:38:55
36.08
10.57
3.41
50°C
3:22:52
42.16
13.49
3.13
55°C
4:08:56
46.20
16.55
2.79
+20°C
45°C
8:09:36
36.08
10.92
3.30
50°C
3:29:38
42.16
13.94
3.02
55°C
4:17:14
46.20
17.11
2.70
+15°C
45°C
2:34:29
36.08
10.27
3.51
50°C
3:17:12
42.16
13.11
3.22
55°C
4:01:59
46.20
16.09
2.87
+12°C
45°C
2:37:40
36.08
10.48
3.44
50°C
3:21:16
42.16
13.38
3.15
55°C
4:06:58
46.20
16.42
2.81
+7°C
45°C
2:34:29
36.08
10.27
3.51
50°C
3:17:12
42.16
13.11
3.22
55°C
4:01:59
46.20
16.09
2.87
+2°C
45°C
3:01:10
36.08
12.05
3.00
50°C
3:51:15
42.16
15.38
2.74
55°C
4:43:46
46.20
18.87
2.45
+0°C
45°C
3:02:53
36.08
12.16
2.97
50°C
3:53:27
42.16
15.52
2.72
55°C
4:46:28
46.20
19.05
2.43
-2°C
45°C
3:01:57
36.08
12.10
2.98
50°C
3:52:16
42.16
15.45
2.73
55°C
4:45:01
46.20
18.95
2.44
-7°C
45°C
3:05:38
36.08
12.34
2.92
50°C
3:56:58
42.16
15.76
2.68
55°C
4:50:47
46.20
19.34
2.39
-10°C
45°C
3:08:43
36.08
12.55
2.88
50°C
4:00:54
42.16
16.02
2.63
55°C
4:55:36
46.20
19.66
3.35
-15°C
45°C
3:13:51
36.08
12.89
2.80
50°C
4:07:28
42.16
16.46
2.56
55°C
5:03:40
46.20
20.19
2.29
-20°C
45°C
3:19:00
36.08
13.23
2.73
50°C
4:14:01
42.16
16.89
2.50
55°C
5:11:43
46.20
20.73
2.23
• Based on peak cut setting 70%
• Please note: The data mentioned in this document is obtained by calculation.
Please use only for reference.
• Equivalent tubing length: 7.5 m, Difference of elevation: 0 m