32
PAW-VP•LDHW - Technical Manual – 2020-07
Performance Characteristic Tables
3
3 Performance Characteristic Tables
The following tables refer to the heating up of the water without reheating and can not be com-
part with Tapping profile data tables.
How to read the following tables:
3.1 Capacity table PAW-VP1000LDHW (10 °C)
City water inlet temp:
10 °C
Outdoor unit type:
U-250PE2E8A
Tank type:
PAW-VP1000LDHW
Ambient
temperature
Water temp
Time
Heating Capacity Power Input
COP
WB
Set temp
[h:m:s]
[kWh]
[kWh]
[kWh / kWh]
+7°C
45°C
2:41:04
38.27
10.71
3.57
50°C
3:23:47
44.34
13.55
3.27
55°C
4:08:34
48.38
16.53
2.93
The example table refers to a supply water temperature of 10°C.
The water in the tank is heated from 10°C to 50°C at an ambient temperature of 7°C. The heat
-
ing phase takes 3:23:47h.
(Without tapping)
In practice, the cycle described above is valid during commissioning. If system design in ac
-
cordance with local conditions, then in the rarest cases so much water is tapped that the tank is
completely emptied and filled with fresh water.
Temperature layering
Tapping amount 50°C*
PAW-VP1000LDHW
[°C]
[ltr.]
>65°C
0.00
>60°C
212.75
>55°C
44.62
>50°C
227.30
>45°C
115.43
>40°C
94.09
The table on the left side shows
the total water volume for each
temperature layer within the tank.
The indication Tapping amount
50°C refers to the compressor
cut-off temperature.
•
212.75 liters of water can
be tapped at temperatures
above 60°C.
•
44.62 liters of water can be
tapped at temperatures below
60°C and above 55°C.
<60°C –
<55°C –
<50°C –
<45°C –
<40°C –
<60°C –
212.75 ltr.
44.62 ltr.
227.30 ltr.
115.43 ltr.
94.09 ltr.
238.81 ltr.