PAW-VP•LDHW - Technical Manual – 2020-07
Electrical Heater
11
11.1.3 Legionella protection cycle
Please observe all local and national regulations and requirements regarding legionella, valid in
your application and installation area.
●
It is recommended that no less than once per week, the heating element is acti-
vated until a minimum tank temperature of 63°C is reached.
●
Minimum ON time 3 hrs.
●
10 amps for VP750 and VP1000LDHW and connected to poles for contactor A1-A2
Digital weekly DIN rail mounting time switch
1 program consists of 1 ON and 1 OFF time and the allocation of any
day of the week or a combination of days and the selected channel.
Example:
1. Prog.: ON 03:00h
OFF 06:00h MO
2. Prog.: ON 03:00h
OFF 06:00h FR
!
Important
Adjust the thermostat for the immersion heater to the desired setpoint. Minimum setpoint must
always apply.
* The DIN rail time switch is for illustrative purposes only. It is the installers responsibility to select a suitable timer
controller matching with the electrical ratings indicated above.
230 V 1 phase 50 Hz
230 V 1 phase 50 Hz
DIN rail time switch*
DIN rail time switch*
Electric heater
3 Pole contactor