90
Control
3.
Confi rm the new setting by pressing the
button.
1 x briefl y
The PV display now shows “nun”, while the SV display now shows “3”.
4. Press the
button repeatedly to select the entry “PSL”.
repeatedly
5. Use the
and
buttons to change the value to either “0” (= factory setting) for „hea-
ting mode“ or “1” for „cooling mode“.
6.
Confi rm the complete parametrization by pressing and holding the
button for approxi-
matedly 3 seconds.
1 x for 3 sec.
✔
Parametrization is now complete. The PV and SV displays have returned to showing the cur-
rent temperature and the set temperature values respectively.
Switching from 0–10 V to 2–10 V output signals
The voltage range for the output signals on terminals 6–7 is factory-set to 0–10 V.
Switching the voltage range from 0–10 V to 2–10 V is possible. However, Panasonic recom-
mends to keep the factory setting.
To switch from 0–10 V to 2–10 V output signals, perform the following steps:
1. Press and hold the
and
buttons jointly for approximately 5 seconds.
1 x 2 buttons for 5 sec.
The PV display shows “PAS”, while the current setting (“0”) in the SV display is blinking.
Note:
After 30 seconds of idleness, the display automatically returns from parametrization
view to normal view.
2. Use the
,
and
buttons to change the value to “–72” (minus 72).