3 types of AHU Kit: Deluxe, Medium and Light.
Model Code
IP 65
0-10V demand
control*
Outdoor temperature shift
compensation. Cold draft prevention
PAW-280PAH2
Yes
Yes
Yes
PAW-280PAH2M
Yes
Yes
No
PAW-280PAH2L
Yes
No
No
* With CZ-CAPBC2.
3
2
1
4
5
6
7
8
System & regulations. System overview
1. AHU Kit equipment (Field supplied)
2. AHU Kit system controller (Field supplied)
3. AHU Kit controller box (with control PCB)
4. Thermistor for Gas pipe (E2)
5. Thermistor for Liquid pipe (E1)
6. Thermistor for Suction air
7. Inter-unit wiring
8. Outdoor unit
Optional parts: Following functions are available by using different control accessories:
CZ-RTC4 Timer remote controller.
· Operation-ON/OFF
· Mode select
· Temperature setting
* Fan operation signal can be taken from the PCB.
PAW-OCT, DC12 V outlet. OPTION terminal.
· Output signal= Cooling/Heating/Fan status
· Defrost
· Thermostat-ON
CZ-CAPBC2 Mini seri-para I/O unit (advanced version only).
· Easy integration in external AHU control systems and BMS
· Demand control: 40 to 115 % (5 % steps) of nominal current by 0–10 V
input signal*
· Target temperature setting by 0–10 V or 0–140
Ω
input signal*
· Mode select or/and ON/OFF control
· Fan operation control
· Operation status output/ Alarm output
· Thermostat ON/OFF control
* Demand control by external BMS cannot be combined with the demand control or target temperature
setting accomplished by the thermostat. However, if simultaneous demand control and target temperature
setting is needed, this can only be achieved by using a second (optional) CZ-CAPBC2 interface.
CZ-T10 terminal / PAW-T10 PCB to connect to T10 connector.
· A Dry contact PCB has been developed to easily control the unit
· Input signal operation ON/OFF
· Remote control prohibition
· Output signal Operation ON status maximum 230 V 5 A (NO/NC)
· Output signal alarm status max. 230 V 5 A (NO/NC)
· Alarm output (by DC12V)
· Additional available contacts:
- External humidifier control (ON/OFF) 230 VAC 3 A
- External fan control (ON/OFF) 12V DC
- External filter status signal potential free
- External float switch signal potential free
- External leakage detection sensor or TH. OFF contact potential free
(possible usage for external blow out temperature control)
PCB, Power trans,
Terminal block
AHU Connection Kit
Standard wired remote controller.
Thermistor x2
(Refrigerant: E1, E2)
Thermistor
(Air: TA; 1 sensor)
1. Remote control CZ-RTC4
2. New plastic IP 65 Box
3. PAW-T10 PCB for Dry Contact
4. 0-10V demand control PCB
5. Intelligent thermostat for:
· Cold draft prevention
· Outdoor temperature shift compensation
6. Terminal base for sensors and power supply
SET
AL1
OUT
ATU
PV
SV
ºC
ºC
Air volume
Dimensions
Piping length
Elevation difference (in/out)
Piping connections
AHU connection kit / System combination
Min / Max
H x W x D
Min / Max
Max
Liquid pipe
Gas pipe
Outdoor unit capacity
AHU
m³/min
mm
m
m
Inch (mm)
Inch (mm)
5,00kW
PAW-280PAH2
8,00 / 13,00
404 x 425 x 78
5 / 30
10
1/4 (6,35)
1/2 (12,70)
6,00kW
PAW-280PAH2
9,00 / 16,00
404 x 425 x 78
5 / 30
10
3/8 (9,62)
5/8 (15,88)
7,50kW
PAW-280PAH2
12,00 / 25,00
404 x 425 x 78
5 / 30
10
3/8 (9,62)
5/8 (15,88)
10,00kW
PAW-280PAH2
14,00 / 33,00
404 x 425 x 78
5 / 30
10
3/8 (9,62)
5/8 (15,88)
12,50kW
PAW-280PAH2
19,00 / 35,00
404 x 425 x 78
5 / 30
10
3/8 (9,62)
5/8 (15,88)
14,00kW
PAW-280PAH2
19,00 / 35,00
404 x 425 x 78
5 / 30
10
3/8 (9,62)
5/8 (15,88)
20,00kW
PAW-280PAH2
28,00 / 66,00
404 x 425 x 78
5 / 70
10
3/8 (9,62)
1 (25,40)
25,00kW
PAW-280PAH2
38,00 / 74,00
404 x 425 x 78
5 / 70
10
1/2 (12,70)
1 (25,40)
AHU PACi Elite
Cooling capacity
Heating capacity
Dimensions
Piping length
Elevation difference (in/out)
Nominal
Nominal
H x W x D
Min / Max
Max
kW
kW
mm
m
m
PAW-280PAH2
6,00 / 25,00
7,00 / 28,00
404 x 425 x 78
5 / 30*
10
PAW-PAW-280PAH2
50,00
56,00
404 x 425 x 78
5 / 30*
10
* For U-200PE2E8A and U-250PE2E8A.
Air flow rate m³/min
Outdoor unit
8,00 8,33 9,00 10,00 10,83 11,67 12,00 13,00 13,33 14,00 15,00 16,00 16,67 18,00 19,00 20,00 25,00 26,67 28,00 30,00 33,00 35,00 36,00 38,00 40,00 43,33 45,00 50,00 58,33 66,00 66,67 71,67 74,00 75,00 83,33 90,00
5,00kW
6,00kW
7,50kW
10,00kW
12,50kW
14,00kW
20,00kW
25,00kW
Standard range of air flow rate under standard conditions (air intake temperature in cooling mode from 18 to 32°C DB).
Extended range of air flow rate under special conditions (air intake temperature in cooling mode from 18 to 30°C DB).
1
4
2
5
3
6
AHU Kit connects PACi outdoor units to Air Handling Units system.
The Panasonic AHU Kits offer a wealth of connectivity possibilities so can
be easily integrated into many systems.
Application: Hotels, offi ces, server rooms or all large buildings where air
quality control such as humidity control and fresh air and is needed.
259
NEW — COMMERCIAL
03 EU BIGRAC GEN 19.indd 259
5/4/19 9:28