32
Product description
3.5 Technical data
Technical data – AHU Kit
All AHU Kit models
Power source
V / ph / Hz
220 ... 240 / 1 / 50
Rated current consumption
A
0.1
Rated power consumption (max.)
W
18.0
Dimensions (enclosure)
H x W x D
mm
278 x 278 x 180
Net weight
Advanced / Medium
kg
4.25
Light
kg
3.98
Protection class
IP65
Thermostat
(Fitted on advanced versions only: PAW-160/280/560MAH2 and PAW-250PAH2)
Dimensions
W x H x D
mm
48 x 48 x 90 (approximately)
Required void space
mm
85 mm (approximately)
Mounting cut-out
W x H
mm
44 x 44 (DIN 1/16)
Display height
mm
10 (approximately)
Temperature range
measuring / indicating
°C
–50 ... +580 / –50 ... +580
Temperature increments
measuring / indicating
°C
0.1 / 1
Sampling period
sec
< 3
Output signal
factory setting / alternative setting
V
0 ... 10 / 2 ... 10
Input signal
Pt100, 2-/3-wire
Control voltage
V / ph / Hz
85 ... 265 / 1 / 50/60
Ambient temperature (max.)
°C
45
Ambient air humidity (max. in hostile environments)
% RH
85
Quiescent current consumption
W
< 3
Dimensions – AHU Kit
Side view
210
254
278
210
254
278
225
257
225
257
100
130
180
165
115
Ø4.2 x 10
Ø5.2 x 11
25
Ø
7
Front view (transparent cover removed)
Important
Apart from the technical data and limitations given in the following tables, the technical data and
limitations of the relevant outdoor units, local wiring and piping design regulations and approved
best practices need to be observed in installation procedures.