23
Product description
CZ-CAPBC2 Mini seri-para I/O unit (medium and advanced versions only)
●
Easy integration in external AHU control systems and BMS
● Demand control: 40 to 115 % (5 % steps) of nominal current by 0–10 V input
signal
1
»
Medium version: Terminals M2-3, M2-4. Advanced version: Terminals M2-1,
M2-2 in case of using TR-16e; Terminals M2-3, M2-4 without using TR-16e.
● Target temperature setting by 0–10 V or 0–140 Ω input signal
1
»
Medium and advanced versions: Terminals M2-3, M2-4.
● Suction air temperature (TA sensor) output by 4–20 mA signal
»
Medium version: Terminals PT9, PT10. Advanced version: Terminals M2-1,
M2-2. On CZ-CAPBC2 interface: Terminals 1, 2.
● Mode select and/or ON/OFF control
2
»
Medium and advanced versions: Terminals DI1, DI2, DI3, COM.
●
Fan operation control
2
»
Medium and advanced versions: Terminals DI1, DI2, DI3, COM.
●
Operation status output/ Alarm output
»
Medium and advanced versions: Terminals COM, DO1 / COM, DO2.
● Thermostat ON/OFF control
2
»
Medium and advanced versions: Terminals DI1, DI2, DI3, COM.
1
Demand control by external BMS cannot be combined with the demand control or target temperature setting accom-
plished by the thermostat. However, if simultaneous demand control and target temperature setting is needed, this
can only be achieved by using a second (optional) CZ-CAPBC2 interface.
2
Mode select and/or ON/OFF control cannot be combined with fan operation control nor Thermostat ON/OFF
control. However if simultaneous control of 2 options is needed, this can be achieved by using a second (optional)
CZ-CAPBC2 interface. All 3 options cannot be used at the same time.
PAW-T10 PCB to connect to T10 connector (light and advanced versions only)
●
Dry contact PCB for easy control of the unit
● Operation ON/OFF input signal
»
PAW-T10 terminal I(1); I(2).
● Remote control prohibition
»
PAW-T10 terminal I(3); I(4).
● Operation ON status output signal, maximum 230 V / 5 A (NO/NC)
»
PAW-T10 terminal NC O(5); NO O(6); Potential for both O(7).
● Alarm status output signal, maximum 230 V / 5 A (NO/NC)
»
PAW-T10 terminal NC O(8); NO O(9); Potential for both O(10).
PAW-OCT, DC12 V outlet, OPTION terminal
●
Output signal for Cooling/Heating/Fan status
»
Terminal ON4; ON5; ON6; Potential ON1.
●
Output signal for Defrost operation indication
»
Terminal ON2; Potential ON1.
● Output signal for Thermostat-ON status
»
Terminal ON3; Potential ON1.
Summary of Contents for PAW-160MAH2
Page 3: ...Air Handling Unit Kit Installation Instructions SET AL1 OUT ATU PV SV ºC ºC ...
Page 4: ......
Page 99: ...97 ...
Page 100: ...Notes ...
Page 101: ...Notes ...