Bracket dimension and installation position
Be sure to have enough brackets for the length
of the line. Two kinds of brackets are required:
end brackets and intermediate brackets.
・
If using brackets other than those specified above, brackets of the same or superior strength must be used.
Failure to do so may cause damage due to falling of equipment.
・
When mounting an end tension insulator, place one intermediate bracket 500mm away from the end bracket.
End tension insulator mounting section
Parallel installation
Spanner
■
Open the box and stretch the High-Tro-Reel unit.
■
Cutting the High-Tro-Reel unit to the length of the line.
High-Tro-Reel length= A−500mm
Distance between brackets, A
Hexagonal bolt (M10×30mm)
Cut the High-Tro-Reel
unit to 500mm shorter
length from the distance
between the brackets
at both ends (the range
of practical collector
s1m).
Bracket position
Hanger should be mounted on the bracket
beforehand on the ground.
●
Cardboard box
●
Crate
1
2
3
1
2
<30m and 50m coil>
<10m coil>
High-Tro-Reel unit
High-Tro-Reel unit
High-Tro-Reel unit
Take the High-Tro-Reel unit out of
the box and roll it out.
Stand the box upright and
pull the High-Tro-Reel unit
out from the botto
Lay the box horizontally
and pull the High-Tro-
Reel unit out of the box.
Notes
・
When installing two or more High-Tro Reel lines, reinforce end tension
insulator brackets by increasing angle size by one step.
Failure to do so may cause damage due to falling of equipment.
Notes
・
Make sure brackets are parallel to the line.
Failure to do so may cause poor connect arm contact.
Notes
・
Be careful that the end of the High-Tro-Reel unit doesn’t swing up.
・
Be careful not to step on or band the Hight-Tro-Reel unit on the ground as this
may damage the unit.
Failure to do so may cause damage
Notes
High-Tro-Reel length= A-200mm
Distance between brackets, A (Less than 30m)
(For transverse)
1
Mounting hangers on the bracket
2
Stretching and cutting the High-Tro-Reel unit
Point of installation
Type and use of brackets
Angle dimensions
For hangers
For end tension insulators
High-Tro-Reel unit installation method
4000
2000
Standard installation (general use)
Horizontal installation
End tension
insulator bracket
End tension
insulator bracket
about
500mm
about
500mm
Intermediate bracket for hangers
20
20
Center of 11mm hole
A
B
A
20
End tension insulator bracket
250
〜
300mm
11mm hole
Interval between hangers( )(mm)
−40×40×5
−75×40×5
Intermediate bracket for hanger
Stay angle (for reinforcement)
11mm hole
End tension insulator bracket
250
〜
300mm
about 500mm
A
250
〜
300mm
90
110
130
3P
4P
5P
130
Unit : mm
150
170
A
B
11mm hole
■ Mounting the bracket
[ unit: mm ]
●
End tension insulator
(for none terminal)
Applies tension to
the High-Tro-Reel unit, and
absorbs sag,expansion and contraction.
■
Ceoss-section
■
Products outline
Notes
14
14
〈90A〉
56
20
20
20
20
20
20
20
96
14
20
20
76
14
14
14
14
Cross-section
Unit : mm
Unit : mm
Unit : mm
5P
4P
3P
56
76
20
20
20
14
20
20
14
20
20
96
14
20
20
14
14
Cross-section
Cross-section
5P
4P
4P
3P
76
20
20
20
15
14
56
20
20
15
14
3P
〈150A・200A〉
●150A.PVC75
200A.PVC95(Heatproof)
〈60A〉
25
mm
25
mm
length of the line laid down
Use joiner maximum 100m
Without joiner maximum 50m
Installation Procedures for High-Tro-Reel <Tension Type>
■
Installation procedure
M10
12
※90
※※107
※
90
※※
107
25
25
●
Downward installation
●
Horizontal installation
Collector arm mount rod, 25mm
×
25mm
(not included)
12
Asterisk (
※
) indicates the conductor sliding surface.
The asterisk (
※※
) indicates the dimensions at the hanger mounting bracket section.
Collector arm mount rod, 25mm
×
25mm
(not included)
40 or
more
●
End tension insulator
(Putting under cable)
On both supply and tightening of the body.
●
Collector arm
Collects power during travel. Able to travel at
300m/min. on a straight section.
●
Joiner
Connects the High-Tro-Reel units together in
long installations.(more then 50m) Can also
feed power to 60A and 90A High-Tro-Reel units.
●
Hanger
Fixes the High-Tro-Reel units to a building structure at
an interval of 4m or less for standard installations, and
2m or less for horizontal installations.
●
Center feed-in joiner
Connect the High-Tro-Reel unit together in long installations.
Can also feed power to 150A and 200A High-Tro-Reel unit.
The lead-in-side set up a hanger at 450
〜
550 mm,
the other side set up a hangar at 550
〜
750 mm
●
High-Tro-Reel unit (tension type)
3P, 4P, 5P; 600V; 60A, 90A
3P, 4P; 150A, 200A
10m, 30m, 50m/coil
Please see below 24P. when use CE type
2.The collector arm mount rod
must be properly mounted
without any twisting.
1.When collector arm mount rod set up a reference
position, the operating range from 70mm
〜
110mm of collector arm set up to be twisting.
3.Set it up so that the collector
arm mount rod may become
parallel to the high tro-reel
unit.
90
mm
Within 2mm
Within 2mm
110mm
Collector arm mount rod
70mm