● In the moving average, obtain output (moving average value) from the following input.
Input: The number of average times, analog input data for the number of average times, the
latest analog input data, and old analog input data
Output: Moving average value
■
Processing during moving average
Average processing example: "Moving average" is set to 15 for the number of average times.
Analog signal
a
b
c d
e
f
g
h
i
j
k
l
m
n
o p q
r
Analog input
processing
Analog input
data
Average of a to o
Average of b to p
Average of c to q
・・・
・・・
・・・
■
Analog_8IN parameters
Name
Default
Description
Averaging process
Not execute
Select "Moving average".
Average constant
200
Specify the number of averaging times.
Count: 2 to 2,000 [times]
5.2 Average Processing Settings