9.1 What to Do If an Error Occurs (Analog Input)
9.1.1 Failure in Reading Analog Input Data
■
Situation
There is a failure in reading analog input data.
■
Solution
1.
Check again that I/O mapping allocations are correct.
2.
Check again the connections of the terminal block.
3.
Check again the parameter settings.
9.1.2 Unstable Analog Input Values
■
Situation
The analog input value is not stable.
■
Solution
1.
Check that a twisted pair shield wire is used and that the wire is properly shielded.
2.
Check that the analog input wiring is not placed close to AC lines or high-tension lines or
bundled with the lines.
3.
Check that there are no power lines, high-tension lines, high-capacity relays, or noise-
generating equipment, such as inverters, close to the analog input unit.
4.
Check that the voltage or current for the range setting is set correctly.
9.1.3 No Proper Conversion Values Obtained with Current Input
■
Situation
Proper conversion values cannot be obtained with current input.
■
Solution
1.
Check again the connections of the terminal block.
2.
Check again the connections of the output equipment.
3.
Check that the range setting is the current mode.
9.1 What to Do If an Error Occurs (Analog Input)
9-2
WUME-GM1AIO-01
Summary of Contents for GM1 Series
Page 2: ...MEMO 2 WUME GM1AIO 01...
Page 4: ...MEMO iv WUME GM1AIO 01...
Page 8: ...MEMO viii WUME GM1AIO 01...
Page 12: ...MEMO 1 4 WUME GM1AIO 01...
Page 18: ...MEMO 2 6 WUME GM1AIO 01...
Page 26: ...MEMO 3 8 WUME GM1AIO 01...
Page 38: ...MEMO 4 12 WUME GM1AIO 01...
Page 58: ...MEMO 5 20 WUME GM1AIO 01...
Page 68: ...MEMO 6 10 WUME GM1AIO 01...
Page 84: ...MEMO 9 4 WUME GM1AIO 01...
Page 94: ...MEMO App 4 WUME GM1AIO 01...
Page 96: ...MEMO WUME GM1AIO 01...
Page 97: ...MEMO WUME GM1AIO 01...
Page 98: ...Panasonic Corporation 2021 August 2021 WUME GM1AIO 01...