FP
Σ
User's Manual
4.3 FP
Σ
Memory Expansion Unit
51
4.3.2.1 F150_READ
instruction
Variable
Data type
Function
s1_BankSlot
INT, WORD
1
Upper byte = bank number: 16#00–16#FF
2
Lower byte = slot number: 16#00–16#1F
s2_Start
INT, WORD
Starting address in specified bank (source address). Range: 0-1023 (16#0–
16#3FF).
n_Number
INT
Number of words to be read. Range: 1–1024 (16#1–16#400).
d_Start
INT, WORD
Starting address in CPU (target address)
EXAMPLE
POU Header
LD Body
When Start turns to TRUE, 10 words are read from bank number 16#50 of the memory
expansion unit located in slot 3, beginning at the address 500, and stored in the array
DestAddrCPU.
Summary of Contents for FPS Series
Page 7: ......
Page 17: ......
Page 18: ...Chapter 1 Safety Measures...
Page 21: ......
Page 22: ...Chapter 2 Overview...
Page 32: ...Chapter 3 CPU Types...
Page 47: ...CPU Types FP User s Manual 30 LD Body...
Page 51: ...CPU Types FP User s Manual 34 POU Header and LD Body...
Page 55: ...CPU Types FP User s Manual 38 LD Body...
Page 57: ......
Page 58: ...Chapter 4 Expansion...
Page 73: ......
Page 74: ...Chapter 5 I O Allocation...
Page 81: ......
Page 82: ...Chapter 6 Installation and Wiring...
Page 115: ......
Page 116: ...Chapter 7 High Speed Counter and Pulse Output...
Page 169: ......
Page 170: ...Chapter 8 Communication...
Page 227: ...Communication FP User s Manual 210 LD Body ST Body...
Page 233: ...Communication FP User s Manual 216 POU Header LD Body...
Page 236: ...FP User s Manual 8 6 Program Controlled Communication 219 POU Header LD Body 1 2...
Page 237: ...Communication FP User s Manual 220 2 2 ST Body...
Page 266: ...Chapter 9 Security Functions...
Page 273: ......
Page 274: ...Chapter 10 Other Functions...
Page 277: ......
Page 278: ...Chapter 11 Troubleshooting...
Page 289: ......
Page 290: ...Chapter 12 Appendix...