Programming Information for Control FPWIN Pro
FMU Technical Manual
44
ErrEvent
Explanation
Source of error
Recommendation
50
Length in COS or cyclic device
response unequal to produced
connection size.
Device
51
UCMM group not supported.
Device
Change the UCMM group.
52
Device keying failed: vendor ID
mismatch.
Device/configuration
Check vendor ID configured with
device's vendor ID.
53
Device keying failed: device type
mismatch.
Device/configuration
Check device type configured
with device's device type.
54
Device keying failed: product code
mismatch.
Device/configuration Check product code configured
with device's product code.
55
Device keying failed: revision
mismatch.
Device/configuration
Check revision configured with
device's revision.
59
Double device address configured in
current configuration.
Configuration
Each device in DeviceNet must
have its own MAC ID.
60
Whole size indicator of one device
data set is corrupt.
Configuration
Download error in the current
database. Contact technical
support.
61
Size of the additional table for
predefined master-slave connections
is corrupt.
Configuration
Download error in the current
database. Contact technical
support.
62
Size of predefined master-slave I/O
configuration table is corrupt.
Configuration
Download error in the current
database. Contact technical
support.
63
Predefined master-slave I/O
configuration does not correspond to
the additional table.
Configuration
Number of I/O units and the
number of configured offset
addresses are different.
64
Size indicator of parameter data table
is corrupt.
Configuration
Value of size indicator too small.
65
Number of inputs declared in the
additional table does not correspond
to the number in the I/O configuration
table.
Configuration
Each entry in the I/O
configuration must have only one
entry in the additional table.
66
Number of outputs declared in the
additional table does not correspond
to the number in the I/O configuration
table.
Configuration
Each entry in the I/O
configuration must have only one
entry in the additional table.
67
Unknown data type in I/O
configuration detected.
Configuration
Data types supported:
BOOL, BYTE, WORD, DWORD
and STRING only.
68
Data type of a defined I/O unit in a
connection does not correspond with
the defined data size.
Configuration
The following types and size are
valid:
•
BOOLEAN = 1 byte
•
Unit 8 = 1 byte
•
Unit 16 = 2 bytes
•
Unit 32 = 4 bytes
69
Output address configured for one unit
exceeds the possible address range of
3584 bytes.
Configuration
The process data image is
limited to 3584 bytes.
Summary of Contents for FMU
Page 1: ...programmable logic controller FMU Technical Manual ...
Page 3: ......
Page 9: ......
Page 10: ...Chapter 1 Features and Restrictions ...
Page 13: ......
Page 14: ...Chapter 2 Parts and Functions ...
Page 23: ......
Page 24: ...Chapter 3 Specifications ...
Page 30: ...Chapter 4 Installation and Wiring ...
Page 42: ...Chapter 5 Programming Information for Control FPWIN Pro ...
Page 70: ...Chapter 6 Outline Dimensions ...
Page 73: ......
Page 76: ...Record of Changes Manual No Date Description of changes ACGM0161V10EN July 2008 First edition ...