FMU Technical Manual
4.4 Wiring of the FP-FMU Connectors
29
2. Wrap the end of the cable with 38mm (1.5in.) of shrink wrap, covering part of
the exposed conductors and part of the trunk line insulation.
38mm
Shrink wrap
Jacket
3. Strip 8.1mm (0.32in.) of the insulation from the end of each of the insulated
conductors.
8.1mm
Shrink wrap
Jacket
4. Insert each conductor into the appropriate clamping cavity of the open style
connector or the screw terminal on the device, according to the color of the
cable insulation:
Wire color
Wire identity
Usage
White CAN_H
Signal
Blue CAN_L
Signal
Bare Drain
Shield
Black V-
Power
Red V+
Power
5. Tighten the clamping screws to secure each conductor. The male contacts of
the device connector must match the female contacts of the connector.
NOTES
•
When removing the wire's insulation, be careful not to scratch the core wire.
•
Do not twist the wires to connect them.
•
Do not solder the wires to connect them. The solder may break due to
vibration.