Programming Information for Control FPWIN Pro
FMU Technical Manual
40
ErrEvent
Explanation
Source of error
Recommendation
receive process data.
63
Unknown process data handshake.
Warm start
Check warm start parameters.
64
Free RAM exceeded.
FMU
Contact technical support.
65
Faulty slave parameter data sets.
Project planning
Contact technical support.
202
No segment for treatment free.
FMU
Contact technical support.
212
Faulty reading of database.
FMU
Download database again.
213
Structure surrender to operating system
faulty.
FMU
Contact technical support.
220
Software watchdog error.
Host
Check host program.
221
No data acknowledgement in process
data handshake mode 0.
Host
Host program did not
acknowledge the last handshake
in time.
222
Master in auto-clear mode.
Slave
Auto-clear mode was activated
because one slave was missing
during runtime.
225
No further segments.
FMU
Contact technical support.
The following error numbers are valid for the error event if "Error remote address" is not equal to
255.
ErrEvent
Explanation
Source of error
Recommendation
2
Station reports overflow.
Master telegram
Check length of configured slave
configuration or parameter data.
3
Request function of master not
activated in the station.
Master telegram
Check slave if PROFIBUS DP
norm compatible..
9
No answer even though slave must
respond.
Slave
Check configuration data of the
station and compare it with the
physical I/O data length.
17
No response from station.
Slave
Check bus cable. Check bus
address of slave.
18
Master not in the logical token ring.
FMU
Check master's fieldbus data link
address or the highest station
address of other master systems.
Check bus cable for short
circuits.
21
Faulty parameter in request.
Master telegram
Contact technical support.
Summary of Contents for FMU
Page 1: ...programmable logic controller FMU Technical Manual ...
Page 3: ......
Page 9: ......
Page 10: ...Chapter 1 Features and Restrictions ...
Page 13: ......
Page 14: ...Chapter 2 Parts and Functions ...
Page 23: ......
Page 24: ...Chapter 3 Specifications ...
Page 30: ...Chapter 4 Installation and Wiring ...
Page 42: ...Chapter 5 Programming Information for Control FPWIN Pro ...
Page 70: ...Chapter 6 Outline Dimensions ...
Page 73: ......