94
Installation Manual
Specifications
GENERAL SPECIFICATIONS
Product weight
265 to 750 lbs
Product dimensions (H x W x D)
24.2" x 42.5" x 10" (Per enclosure)
IP degree of protection
NEMA Type 1/IP20
Temperature
Operating: -20 to 55°C (0°C Min Startup Temp. & power derated above
40°C )
Storage: -25 to 70°C (-13 to 158°F)
Compliances
STANDARD COMPLIANCE
Safety: UL9540, UL1973, UL1741SA, CSA 22.2
Grid Connection Standards: IEEE 1547A, IEEE 1547.1
Emissions: FCC part15 class B
Standards: Rule 21, HECO
EFFICIENCY
Peak Battery to Grid
94.7%
System Standby Power
20W
System Idle Power
< 8W
AC INPUT FROM GRID (GRID SUPPORT)
Automatic Transfer Power Rating /
Typical Transfer Time
7000W / 20ms
Input Voltage Range
L-L: 180 to 280V (240V nominal)
Input Frequency Range
45 to 54.9Hz / 55 to 65Hz
AC OUTPUT TO GRID (GRID SUPPORT)
Output Power (Continuous)
@ 25°C
5000W
Grid Feed-In Current Range
0 to 24A (@240V)
Grid Feed-In Voltage Range
L-L: 211 to 264V ± 3.0V
Grid Feed-In Frequency Range
49.3 to 50.5Hz / 59.3 to 60.5Hz ± 0.05Hz
DC BATTERY CHARGER
Max Charge/Discharge Current
100A/150A
Output Voltage Range
44 to 58V (48V Nominal)
Compatible Battery Types
Li-Ion