TIMER TABLE
Test Mode
Name
Time
(When test point
Remarks
Short-circuited)
Real Timer
1 hr.
1 min.
10 min.
10 sec.
1 min.
1 sec.
Time Delay Safety Control
2 min. 58 sec.
0 sec.
Forced Operation
60 sec.
0 sec.
Time Save Control
7 min.
42 sec.
Anti-Freezing
4 min.
0 sec.
Auto Mode Judgement
25 sec.
0 sec.
Soft Dry
OFF
6 min.
36 sec.
ON
10 min.
60 sec.
Soft Dry: 10 min. operation
Cooling
40 sec.
4 sec.
70 sec.
7 sec.
Deodorizing Control
20 sec.
2 sec.
180 sec.
18 sec.
Soft Dry
40 sec.
4 sec.
360 sec.
36 sec.
Comp. Reverse Rotation Detection
5 min.
30 sec.
Comp. ON 5 min. and above
2 min.
0 sec.
Comp./ Fan Motor Delay Timer
1.6 sec.
0 sec.
Powerful Mode Operation
15 min.
15 sec.
Random Auto Restart Control
0 ~ 62 sec.
0 ~ 6.2 sec.
Ion OFF Timer
30 min.
180 sec.
Ion ON Timer
10 sec.
1 sec.
Quiet operation timer
1 hr. 30 min.
9 sec.
Summary of Contents for CS-V28EKE CU-V28EKE
Page 8: ...8 4 Location of Controls and Components Indoor Unit Outdoor Unit Remote Control ...
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 10: ...10 5 2 Outdoor Unit ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 13: ...13 8 Wiring Connection Diagram ...
Page 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit BOTTOM VIEW ...
Page 15: ...15 TOP VIEW ...
Page 16: ...16 9 2 Indicator And Receiver BOTTOM VIEW TOP VIEW ...
Page 20: ...20 This can be used for left rear piping and left bottom piping also ...
Page 43: ...43 15 Technical Data 15 1 Thermostat Characteristics ...
Page 45: ...45 15 3 Operation Characteristics 15 3 1 CS V28EKE CU V28EKE ...
Page 46: ...46 ...