29
- Indoor fan motor operate at low fan speed or QLo.
• This control is cancelled immediately when above condition is changed.
• Dew prevention is control by:
1. Lo fan speed
Lo fan is changed to Lo+ fan
2. QLo fan speed
11.5. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
11.5.1.
Fan Speed Rotation Chart
Speed
CS-V28EKE
Cool, Dry
S Hi
1760
Hi
1720
Me
1590
Lo+
1500
Lo
1410
Lo-
1200
S Lo
960
Q Hi
1620
Q Me
1480
Q Lo
1310