10.4.4.
CONNECT THE CABLE TO THE OUTDOOR UNIT
(FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT)
1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1.5 mm
2
flexible
cord, type designation 245 IEC 57 or heavier cord.
3. Secure the cable onto the control board with the holder (clamper).
4. Cable connection to the power supply (220-240V, 50Hz) through knife switch (Disconnecting means).
• Connect the approved polychloroprene sheathed power supply cable 3 × 4.0 mm
2
(V28EK), type designation 245 IEC 57 or
heavier cord to the terminal board, and connect the other end of the cable to knife switch (Disconnecting means).
Note
: Knife switch (Disconnecting means) should have minimum 3.5 mm contact gap.
●
Secure the cable onto the control board with the holder (clamper).
Summary of Contents for CS-V28EKE CU-V28EKE
Page 8: ...8 4 Location of Controls and Components Indoor Unit Outdoor Unit Remote Control ...
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 10: ...10 5 2 Outdoor Unit ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 13: ...13 8 Wiring Connection Diagram ...
Page 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit BOTTOM VIEW ...
Page 15: ...15 TOP VIEW ...
Page 16: ...16 9 2 Indicator And Receiver BOTTOM VIEW TOP VIEW ...
Page 20: ...20 This can be used for left rear piping and left bottom piping also ...
Page 43: ...43 15 Technical Data 15 1 Thermostat Characteristics ...
Page 45: ...45 15 3 Operation Characteristics 15 3 1 CS V28EKE CU V28EKE ...
Page 46: ...46 ...